Capacity data - dx (mechanical) cooling, Operating limits, Logicool ™ chillers – Airedale LogiCool FreeCool 40kW User Manual

Page 20: Performance data

Advertising
background image

LOGICOOL

Chillers

20

Chillers

Technical Manual : 6521355 V1.8.0 07/2014

Performance Data

CAPACITY DATA - DX (MECHANICAL) COOLING

Cooling Duty

Ambient

Entering / Leaving

Water Temperature °C

25°C

30°C

35°C

40°C

Output kW

Input kW Output kW

Input kW Output kW

Input kW Output kW

Input kW

LCC20

10 / 5

18.7

6.0

18.1

6.4

17.1

7.0

16.2

7.5

11 / 6

19.3

6.0

18.7

6.4

17.7

7.0

16.8

7.6

12 / 7

19.9

6.0

19.2

6.4

18.2

7.1

17.3

7.6

15 / 10

21.8

6.1

21.0

6.6

19.8

7.2

18.8

7.7

17 / 12

23.2

6.1

22.2

6.6

21.0

7.2

19.9

7.8

LCC40

10 / 5

35.6

11.8

33.6

13.0

31.8

14.2

29.9

15.3

11 / 6

36.6

11.9

34.7

13.1

32.8

14.3

30.9

15.4

12 / 7

37.7

12.0

35.7

13.2

33.7

14.4

31.8

15.5

15 / 10

40.9

12.4

38.8

13.5

36.7

14.7

34.7

15.9

17 / 12

43.2

12.6

40.9

13.8

38.8

14.9

36.7

16.1

1

Cooling Duty based on 20% Ethylene Glycol concentration. For alternative concentrations, refer to

Glycol Data

, on page 23.

2

Output kW = DX (Mechanical) Cooling duty.

3

Input kW

= compressor + fan input power.

4

Unit water flow rate (l/s)

=

Output kW

3.9 x

T

5

Interpolate for water temperatures between those quoted, do not extrapolate.

6

For conditions outside those quoted, please refer to Airedale.


OPERATING LIMITS
(For 20% Ethylene Glycol)

Standard Unit

Minimum Ambient Air DB °C

-20°C

Maximum Ambient Air DB °C

Refer to

Capacity Data - DX (Mechanical) Cooling

, above

Minimum Leaving Water Temperature °C

+5°C

Maximum Return Water Temperature °C

+20°C

Minimum / Maximum

ΔT

4°C / 8°C

1

For conditions outside those quoted, please refer to Airedale.

All performance data is supplied in accordance with BS EN 14511-1:2013