Badger Meter MR Transmitter User Manual

Page 15

Advertising
background image

Full Flow Rate

The full flow rate is used to span the meter . Its displayed name is FULL FLOW and is viewed or changed using the Numeric

Value Entry Procedure .

Zero Capture

The zero position of the meter cone must be set when installing the meter . To capture the zero calibration position, press

ENTER at the ZERO CAP prompt . NO will display . Press either arrow key to change to YES, then press ENTER to capture zero .

Viscosity Units (Displayed for OIL meters only)

The Viscosity Units parameter is used in conjunction with Viscosity to perform viscosity correction for oil applications . The

meter allows the selection of the viscosity units, SUS or cSt . Its displayed name is VIS UNIT and is viewed or changed using the

List Item Selection Procedure .

Viscosity (Displayed for OIL meters only)

Viscosity is used in conjunction with Viscosity Units to perform viscosity correction for oil applications . Enter the viscosity in

either SUS or cSt, depending on the viscosity units selected, of the oil that will be used . Its displayed name is VISCOSTY and is

viewed or changed using the Numeric Value Entry Procedure .

Operating Pressure Unit (Displayed for GAS meters only)

Operating Pressure Units is used in conjunction with Operating Pressure in gas applications to compensate for the actual

pressure being measured at the meter . The meter allows the selection of the operating pressure units, Bar or PSI . Its displayed

name is PRESUNIT and viewed or changed using the List Item Selection Procedure .

Operating Pressure (Displayed for GAS meters only)

Operating Pressure is used in conjunction with Operating Pressure Units in gas applications to compensate for the actual

pressure being measured at the meter . Enter the operating pressure in either Bar or PSI units, depending on the Operating

Pressure Units selected . Its displayed name is OP PRES and is viewed or changed using the Numeric Value Entry Procedure .

Operating Temperature Unit (Displayed for GAS meters only)

Operating Temperature Units is used in conjunction with Operating Temperature in gas applications to compensate for the

actual temperature of the gas being measured at the meter . The meter allows the selection of the operating temperature

units, °F or °C . Its displayed name is TMP UNIT and is viewed or changed using the List Item Selection Procedure .

Operating Temperature (Displayed for GAS meters only)

Operating Temperature is used in conjunction with Operating Temperature Units in gas applications to compensate for the

actual temperature of the gas being measured at the meter . Enter the operating temperature in either °F or °C, depending on

the Operating Temperature Units selected . Its displayed name is OP TEMP and is viewed or changed using the Numeric Value

Entry Procedure .

Specific Gravity Correction Factor

Specific Gravity is used to compensate for the specific gravity of the liquid or gas being measured with the meter . Its displayed

name is SP GRAV and is viewed or changed using the Numeric Value Entry Procedure .

Damping

The Damping factor is increased to enhance the stability of the flow readings . Damping values are decreased to allow the flow

meter to react faster to changing values of flow . This parameter can range from 0 to 99; factory default is 0 . Its displayed name

is DAMPING and is viewed or changed using the Numeric Value Entry Procedure .

Output Mode

The MR flow transmitter offers three analog output modes:
• 4…20 mA Output Signal
• 0…5 Volts DC Output Signal
• 0…10 Volts DC Output Signal
The output mode selected is determined by the type of peripheral device being connected to the MR flow transmitter .
The displayed name is OUT MODE and is viewed or changed using the List Item Selection Procedure .

OTEE:

N

Setup prompts and descriptors for configuring and calibrating the analog output will correspond to the output

mode selected .

User Manual

Page 15

November 2013