Troubleshooting, No lcd display, No rate or total displayed – Badger Meter MR Transmitter User Manual

Page 18: Unstable flow reading, Figure 9, Om the body

Advertising
background image

TROUBLESHOOTING

No LCD Display

• For 4…20 mA operation, check for current flow in the loop .
• Check polarity of the current loop connections for proper orientation .
• For 0…5V or 0…10V operation, check for proper voltage being supplied to the unit .
• Check polarity of the supply voltage .

MENU

ENTER

RU

N

PR

OGR

AM

REL

A

Y 1

REL

A

Y 2

4

3

2

5

6

7

1

Figure 9: Cartridge components

Number Name

1

Body

2

Cone Assembly

3

Meter Spring

4

Piston Assembly

5

Retaining Spring

6

Cap

7

Wave Spring

No Rate or Total Displayed

• Check flow meter body and internal components for debris . Piston should move inside the tube freely .
• Check setup programming of flow meter .

Unstable Flow Reading

• This usually indicated pulsing or oscillation in the actual flow . Increase the DAMPING parameter to increase the filtering in

order to provide a more stable display reading .

MR Flow Transmitter

Page 18

November 2013