Standby – Blue-White FLEX-PRO A4 ProSeries Peristaltic Pump User Manual
Page 25

Page 25
- Menu
+ Configuration
+ Input Setup
+ Pump Output
<- Esc
- Input Setup
+ Contact Closure Input
- Contact Closure Input
Close: Stop Pump
Open: Stop Pump
<- Esc
Hidden
+ Motor - Select RPM
+ Tubing - Max Flowrate
+ Set FVS
+ Operating Input Modes
Disable
Done
4.4
Contact Closure Input
Used to remotely start and stop pump using a close=stop or open=stop signal. If
pump should start on an open, then select “Close: Stop Pump” option. Can be
used with an external foot pedal, a PLC, contact closure, or other similar
external devices.
Default settings:
Disable
CC Input Range:
6 - 30 VDC
or
Dry Contact Closure (no voltage required)
[See section 5.1 for wire connections]
Navigate to Contact Input menu by MENU button, then selecting Input Setup,
and then Contact Input.
Press UP or DOWN arrow to scroll through your options.
Press ENTER to make a selection. You should then notice radio button (square
box) is now filled in next to your selection.
Press DOWN arrow to scroll down to Done selection. Then press ENTER.
To navigate back out of menus, select <-Esc and press the ENTER button at
bottom of every screen menu until you see Run Mode screen displayed.
IMPORTANT: If Contact Closure Input is enabled, pump will display STANDBY if
pump is in Stop mode via the Contact Closure. Please use caution in this
mode. Pump can Start at anytime. If you must perform maintenance to the
pump, Press STOP button.
When Contact Closure Input is enabled, the word Remote will be displayed on
lower left side of screen at all times.
- Sample Screen Shots -
In Proportional Dosing mode, you can view
current incoming signal count and settings by
pressing RIGHT arrow (see screen shots).
RIGHT arrow is a convenient way to scroll
through multiple read-only screens during
normal operating mode of pump.
Tip!
Proportional Dosing
- Screen Shot -
Proportional Dosing
- Screen Shot -
% Concentration:
12.5
Spec. Gravity:
1.25
300
Hz
Displays current incoming signal
Е
Й
ДИ
Displays current rotor direction
Manual Speed Adjust
GAL/DAY
228
Е
Й
ДИ
REMOTE
Signal started pump
Flex-Pro
Manual Speed Adjust
Waiting for SIGNAL...
STANDBY
REMOTE
Signal stopped pump