Caution on installation location – Dwyer UXF2 User Manual
Page 6

- iv -
(1) Sufficient space is required for daily inspection, proper wiring, etc.
(2) A location not exposed to direct sunshine nor weathering.
(3) Isolation from excess vibration, dust and moisture.
(4) A location not subjected to radiated heat from a heating furnace etc.
(5) A location not subjected to corrosive atmosphere
(6) A location not to be flooded
(7) A place remote from electrical devices (motor, transformer, etc.) which generate electromagnetic
induction noise, electrostatic noise, etc.
(8) A location not subject to excessive fluid pulsation (near pump discharge side)
(9) A location that provides sufficient flow conditioning with the length of the straight pipe.
(10)A place where ambient temperature and humidity are • 20 to +50qC and 90% RH or less for flow
transmitter, and • 20 to +60qC and 90% RH or less for detector set.
CAUTION ON INSTALLATION LOCATION
BULLETIN F-70