This solution is preferable, especially in cases where the switching device only checks its safety outputs in the
course of an enabling cycle, as is the case with some electro-mechanical switching devices. A suitable
checking interval must be specified according to the safety requirements.

NOTE

A separate shielded cable must be used for the "safe pulse block" or "switch-off of the 24V
supply". When using a protective switching device with short-circuit monitored OSSD-outputs,
the safety outputs can be combined in a single cable.

NOTE

Only the "safe pulse block" or "switch-off of the 24V" supply fulfil the requirements of Safety
Category 4. Safety category 1 (and PL c) can be achieved for the digital inputs.

The frequency inverter can only fulfil safety category 1 during the period between activation of
the "safe pulse block" via a digital input and activation via terminals 88 and 89.