10 Technical data

BU 0230 GB-2712

73

10.6 Data for switching off the 24V supply

(only for SK 205E, SK 215E Size 1 to 3)

Function

Specification

Input voltage

+24 V

Voltage tolerance

±25 % (18

V…30 V)

Operation at OSSD

-

10 % +25 % (21.6 V…30 V)

Power consumption

≤ 500 mA (mean value)

For details see Section 24 V supply

Peak current

≤ 1 A (Peak, on switch-on)

≤ 6.5 A (Peak, on OSSD)

For details see Section 24 V supply

Cable length

≤ 100 m (refer to EMC, grouping)

Line capacitance

≤ 2 nF * t

OSSD

/ 0.1 ms per connected inverter

(with t

OSSD

= Width of test pulse, max. 0.5 ms)

Switch-on delay

≤ 3 s

Reaction time

≤ 200 ms (≤ 80 ms typical)

Cycle time

≥ 4 s

Requirements made of OSSDs

Test pulse width ≤ 500 µs

Duty (high level) ≥ 90 %

Distance between double pulses ≥1ms (note the duty factor)

Safety integrity level (IEC 61508)

SIL3

Probability of a hazardous failure per
hour

PFH = 0

Probability of a hazardous failure on
call-up

PFD = 0

Proportion of safe failures

SFF = 100 %

Safety category

(as per to EN ISO 13849-1)

Cat. 4

Performance level
(as per to EN 13849-1)

PL e

The mean time until a hazardous
failure

MTTF

d

= "High" (>100 years)

Diagnostic coverage level

DC cannot be established (PFH=0)

Lifetime

TM = 5 years