PROFINET bus module for NORD frequency inverters SK 5xxE

10

Subject to technical amendments

BU 0590 GB-0312

2.2.2

Technical data

Specification

Max. baud rate 100 MBaud

PROFINET IO

Electrical isolation 500V

eff

Bus connection

2  RJ45

Bus termination

Performed automatically by the SK TU3-… Technology Unit

Cable

Ethernet CAT-5 or better

Max. cable length

100m between two Ethernet bus modules

Supply voltage

24V

 20%, current consumption ≈ 150mA

Reverse polarity protected

Status display

4 LEDs

Device address

via the PROFINET IO controller or parameterisation

PE

Connection via plug pins under the 24V supply

Shield

The shields of the two RJ sockets are connected together and connected to PE with a
high resistance and capacitance. If several technology units are adjacent to each
other, only one board needs to be connected to the PE.

Table 1 Electrical specifications of the SK TU3-PNT


2.2.3

Connections


Name

Name

45

+24V

46

GND

Table 2 Power supply connections

Signal

Name

RJ45 Pin

TX+

Transmission Data +

1

TX-

Transmission Data -

2

RX+

Receive Data +

3

RX-

Receive Data -

6

Table 3 RJ45 socket connections


Pin 1

Pin 8

24V

GND

SK TU3-…

PE