NORD Drivesystems BU0590 User Manual

Page 40

Advertising
background image

PROFINET bus module for NORD frequency inverters SK 5xxE

40

Subject to technical amendments

BU 0590 GB-0312

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter set

P545

Bus actual value 3

(Actual bus value 3)

up to

SK 535E

S P

0 ... 24

{ 0 }

This parameter is identical to P543.

Condition is PPO 2 or PPO 4 type (P507).

P546

Function Bus setpoint 1

(Function of bus - setpoint 1)

up to

SK 535E

S P

0 ... 55

{ 1 }

In this parameter, a function is allocated to the output setpoint 1 during bus actuation.

The possible analog functions can be found in the following table.

NOTE:

For further details please refer to the manual BU0500 (P400, P546), the relevant
BUS operating manual or the supplementary POSICON manual BU0510.

P546

[-01]

...
[-05]

Function Bus setpoint

(Function bus - setpoints)

SK 540E and

above

S P

In this parameter, during bus actuation a function is allocated to the setpoint provided.

NOTE:

The setpoints 4 and 5 must be supported by the relevant bus module. For further
details, please refer to manual BU0500 (P400, P546), the relevant BUS operating
manual or the supplementary POSICON manual BU0510.

[-01] =

Bus setpoint 1

[-02] =

Bus setpoint 2

[-03] =

Bus setpoint 3

[-04] =

Bus setpoint 4

[-05] =

Bus setpoint 5

0 ... 57

{ [-01] = 1 }

all other { 0 }

0 =

Off

1 =

Setpoint frequency

2 =

Torque current limit (P112)

3 =

Actual frequency PID

4 =

Frequency addition

5 =

Frequency subtraction

6 =

Current limit (P536)

7 =

Maximum frequency (P105)

8 =

Actual PID frequency limited

9 =

Actual PID frequency monitored

10 =

Torque servo mode (P300)

11 =

Torque precontrol (P214)

12 = Reserved

13 =

Multiplication

14 =

Process controller actual value

15 =

Process controller setpoint

16 =

Process controller lead

17 =

BusIO In Bits 0...7

18 =

Curve travel calculator

19 =

Set relays, "Output status"
(P434/441/450/455=38)

20 =

Set analog output (P418=31)

21 = …45 reserved from SK 530E and above

BU 0510

46 =

Setval.torque p.reg., "Setpoint torque
process controller"

47 = reserved from SK 530E and above

BU 0510

48 =

Motor temperature (SK 540E and above)

49 = reserved from SK 540E and above

BU 0510

53 =

d-correction F process (SK 540E and
above)

54 =

d-correction Torque (SK 540E and above)

55 =

d-correction F+torque (SK 540E and
above)

56 = reserved from SK 540E and above

BU 0510

57 = reserved from SK 540E and above

BU 0510