2 commissioning the bus module 3.2.1 – NORD Drivesystems BU0590 User Manual

Page 14

Advertising
background image

PROFINET bus module for NORD frequency inverters SK 5xxE

14

Subject to technical amendments

BU 0590 GB-0312

3.2 Commissioning the bus module

3.2.1

Connecting the bus module

 Connect the bus module to the PE via the plug pins
 Connect the 24V supply via the plug-in terminal. Note the consumption of each module

(Technical Data)

 Connect the Ethernet cable

Bus direction

PROFINET

Incoming cable

(from master / controller)

Left or right RJ45 socket

Labelled "1" or "2"

Outgoing cable

Left or right RJ45 socket

Labelled "1" or "2"

Both RJ45 sockets of the PROFINET module are internally connected via a switch.

Table 8 Bus cable connections

 If the bus module is the last participant, the RJ45 socket remains open in the outgoing direction. The

bus connection is performed automatically.

ATTENTION

Each bus module requires a separate PE connection via the plug pin. Otherwise,
interference-free operation of the bus module cannot be guaranteed.

3.2.2

Parameter settings of the frequency inverter

The following settings must be made on the frequency inverter (SK 5xxE):

 Control via

Ethernet TU  P509 = "8"

 Setpoint via

Ethernet TU  P510 = "8" or "0" if P509 = "8"

 Setting of setpoints via

P546, P547 and P548 (SK 500E … SK 535E)

P546 [-01] … [-05] (SK 540E and above)

 Setting of actual values via

P543, P544 and P545 (SK 500E … SK 535E)

P543 [-01] … [-05] (SK 540E and above)

For a detailed description of the parameters, please refer to the frequency inverter operating manual
(BU 0500).
The parameters can be set with NORD parameterisation tools (e.g. NORD CON, SimpleBox) or via the bus
master / controller.

Advertising