HM4 Humidity and Temperature Probe with

Heated Sensor

Instruction Manual

Document Type

Page 22 of 41

Document Title

© 2014; ROTRONIC AG

E-M-HM4-V0_08

In general, signal cables should be installed in bundles or channels / conduits, separate from other cables as

indicated in the table below:

Bus signals such as RS-485

Data signals for PCs, printers, etc.

Shielded analog inputs

Unshielded DC voltage (

≤ 60 V)

Shielded process signals (

≤ 25 V)

Unshielded AC voltage (

≤ 25 V)

Coaxial cables for CRT monitors

in common bundles or channels / conduits

DC voltage from 60 V to 400 V (unshielded)

AC voltage from 25 V to 400 V (unshielded)

in separated bundles or channels / conduits,

without minimum distance

DC and AC voltage > 400 V (unshielded)

Telephone lines

Lines leading into EX-rated areas

in separated bundles or channels / conduits