Amana Gas Furnance S)8 User Manual

Page 20

Advertising
background image

20

G

AS

S

UPPLY

AND

P

IPING

Contact your distributor for a tabular listing of appropriate
manufacturer’s kits for propane gas and/or high altitude instal-
lations. The indicated kits must be used to insure safe and
proper furnace operation. All conversions must be performed
by a qualified installer, or service agency.

G

AS

P

IPING

C

ONNECTIONS

T

O

 

AVOID

 

POSSIBLE

 

UNSATISFACTORY

 

OPERATION

 

PMENT

USE

 

THE

 

PROPER

 

SIZE

 

OF

 

NATURAL

/

PROPANE

 

GAS

 

PIPING

 

NEEDED

 

WHEN

 

RUNNING

 

PIPE

 

FROM

 

THE

 

METER

/

TANK

 

TO

 

THE

 

FURNACE

.

OR

 

EQUIPMENT

 

DAMAGE

 

DUE

 

TO

 

UNDERFIRING

 

OF

 

EQUI

WARNING

When sizing a trunk line, be sure to include all appliances
which will operate simultaneously.

The gas piping supplying the furnace must be properly sized
based on the gas flow required, specific gravity of the gas, and
length of the run. The gas line installation must comply with
local codes, or in their absence, with the latest edition of the
National Fuel Gas Code, NFPA 54/ANSI Z223.1.

Natural Gas Capacity of Pipe

In Cubic Feet of Gas Per Hour (CFH)

Length of

Nominal Black Pipe Size

Pipe in Feet

1/2"

3/4"

1"

1 1/4"

1 1/2"

10

132

278

520

1050

1600

20

92

190

350

730

1100

30

73

152

285

590

980

40

63

130

245

500

760

50

56

115

215

440

670

60

50

105

195

400

610

70

46

96

180

370

560

80

43

90

170

350

530

90

40

84

160

320

490

100

38

79

150

305

460

(Pressure 0.5 psig or less and pressure drop of 0.3" W.C.; Based on
0.60 Specific Gravity Gas)

CFH = BTUH Furnace Input

Heating Value of Gas (BTU/Cubic Foot)

To connect the furnace to the building’s gas piping, the installer
must supply a ground joint union, drip leg, manual shutoff valve,
and line and fittings to connect to gas valve. In some cases,
the installer may also need to supply a transition piece from 1/
2" pipe to a larger pipe size.

The following stipulations apply when connecting gas piping.

Use black iron or steel pipe and fittings for the building
piping.

Use pipe joint compound on male threads only. Pipe
joint compound must be resistant to the action of the
fuel used.

Use ground joint unions.

Install a drip leg to trap dirt and moisture before it can
enter the gas valve. The drip leg must be a minimum
of three inches long.

Install a 1/8" NPT pipe plug fitting, accessible for test
gage connection, immediately upstream of the gas
supply connection to the furnace.

Use two pipe wrenches when making connection to
the gas valve to keep it from turning. The orientation
of the gas valve on the manifold must be maintained
as shipped from the factory.

Install a manual shutoff valve between the gas meter
and unit within six feet of the unit. If a union is installed,
the union must be downstream of the manual shutoff
valve, between the shutoff valve and the furnace.

Tighten all joints securely.

Connect the furnace to the building piping by one of
the following methods:

Rigid metallic pipe and fittings.

Semi-rigid metallic tubing and metallic fittings.
Aluminum alloy tubing must not be used in exterior
locations.

Use listed gas appliance connectors in accordance
with their instructions. Connectors must be fully in
the same room as the furnace.

Protect connectors and semi-rigid tubing against
physical and thermal damage when installed.
Ensure aluminum-alloy tubing and connectors are
coated to protect against external corrosion when
in contact with masonry, plaster, or insulation, or
subjected to repeated wetting by liquids such as
water (except rain water), detergents, or sewage.

Drip Leg

Ground Joint Pipe Union

To Be Installed Ahead of

Gas Valve

Reducing Coupling

1/2” x 1/8” with 1/8”

Pipe Plug to Measure

Line Gas Pressure

Height Required

By Local Code

Location of Manual Valve

(Installed Ahead of

Ground Joint Pipe Union)

``

General Furnace Layout

U

PFLOW

I

NSTALLATIONS

When the gas piping enters through the right side of the fur-
nace
, the installer must supply the following fittings (starting
from the gas valve):

90 degree elbows (2).

Close nipple.

Straight pipe to reach the exterior of the furnace .

Advertising
This manual is related to the following products: