Gas Valve On/Off

Selector Switch

White-Rodgers Model 36G54 (Two-Stage)

Inlet

Pressure

Boss

Low Fire

Regulator

Adjust

Manometer

Manometer

Hose

High Fire Regulator

Adjust

Regulator

Vent

Outlet

Pressure Boss

Open to

Atmosphere

On/Off Switch

High Fire Coil

Terminal (HI)

Coaxial Coil

Terminal (M)

Common

Terminal(C)

White-Rodgers Model 36G54 Connected to Manometer

Gas Valve On/Off

Selector Switch

Regulator

Vent

High Fire

Regulator

Adjust

Low Fire

Regulator

Adjust

Honeywell Model VR9205 (Two-Stage)

i

Manometer

Manometer

Hose

Common
Terminal(C)

High Fire Coil
Terminal (HI)

Low Fire Coil
Terminal (LO)

Inlet Pressure Tap
1/8 NPT

Open to

Atmosphere

Outlet Pressure Tap
1/8 NPT

Honeywell Model VR9205 Connected to Manometer

1. Turn OFF gas to furnace at the manual gas shutoff valve

external to the furnace.

2. Connect a calibrated water manometer (or appropriate

gas pressure gauge) at either the gas valve inlet pressure
boss or the gas piping drip leg. See Honeywell VR9205
gas valve figure or White-Rodgers 36G54 gas valve figure
for location of inlet pressure boss.

NOTE: If measuring gas pressure at the drip leg or Honeywell
VR9205 gas valve, a field-supplied hose barb fitting must be
installed prior to making the hose connection. If using the inlet
pressure boss on the White-Rodgers 36G54 gas valve, then
use the 36G Valve Pressure Check Kit, Goodman Part No.
0151K00000S.

3. Turn ON the gas supply and operate the furnace and all

other gas consuming appliances on the same gas supply
line.

4. Measure furnace gas supply pressure with burners firing.

Supply pressure must be within the range specified in
the Inlet Gas Supply Pressure table.

Natural Gas

Minimum: 5.0" w.c.

Maximum:10.0" w.c.

Propane Gas Minimum: 11.0" w.c.

Maximum:13.0" w.c.

Inlet Gas Supply Pressure

If supply pressure differs from table, make the necessary ad-
justments to pressure regulator, gas piping size, etc., and/or
consult with local gas utility.

5. Turn OFF gas to furnace at the manual shutoff valve and

disconnect manometer. Reinstall plug before turning on
gas to furnace.

6. Turn OFF any unnecessary gas appliances stated in

step 3.