Gme8 b – Amana Gas Furnance S)8 User Manual

Page 42

Advertising
background image

42

GME8

B

LOWER

P

ERFORMANCE

D

ATA

Tons AC

at 0.5"

0.6

0.7

0.8

ESP

CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM CFM CFM

T1 - YELLOW

1.5

875

----

793

----

736

----

674

----

592

----

556

509

460

T2 - RED

2.0

1032

43

965

46

914

49

861

----

810

----

756

712

659

T3 - ORANGE

2.5

1217

37

1153

39

1098

40

1051

42

1009

44

964

918

877

T4 - BLUE

3.0

1365

33

1313

34

1268

35

1221

36

1172

38

1129 1086 1054

T5 - BLACK

3.5

1549

29

1505

30

1460

30

1420

31

1378

32

1350 1305 1268

T1 - YELLOW

2.5

1268

47

1198

49

1151

51

1092

54

1041

57

988

932

883

T2 - RED

3.0

1362

44

1305

45

1261

47

1212

49

1170

51

1121 1074 1021

T3 - ORANGE

3.5

1576

38

1519

39

1473

40

1426

42

1398

42

1341 1290 1252

T4 - BLUE

4.0

1755

----

1711

35

1657

36

1627

36

1579

38

1548 1502 1463

T5 - BLACK

5.0

2183

----

2128

----

2094

----

2060

----

2014

----

1992 1944 1847

T1 - YELLOW

3.0

1466

51

1415

52

1357

55

1306

57

1248

59

1202 1144 1088

T2 - RED

3.5

1642

45

1596

46

1552

48

1499

49

1449

51

1388 1352 1306

T3 - ORANGE

4.0

1750

42

1750

42

1707

43

1667

44

1610

46

1574 1531 1486

T4 - BLUE

4.0

1870

40

1805

41

1782

42

1737

43

1701

44

1656 1606 1571

T5 - BLACK

5.0

2297

----

2297

----

2224

----

2106

35

2014

37

1896 1813 1669

Notes:

(CFM & Temperature Rise vs. External Static Pressure)

0.1

0.2

0.3

0.4

0.5

Model

Heating Speed

As Shipped

Motor Speed

EXTERNAL STATIC PRESSURE (Inches Water Column)

GME81005C***

• CFM in chart is without filter(s). Filters do not ship with this furnace, but must be provided by the installer. If the furnace requires two
return filters, this chart assumes both filters are installed.
• All furnaces ship as high-speed cooling and medium-speed heating. Installer must adjust blower cooling and heating speed as needed.

GME80603B***

GME80805C***

• For most jobs, about 375 - 400 CFM per ton when cooling is desirable.

• Temperature rise data is based on 2nd-stage heat. First-stage heat is 75% of rise indicated above.

• INSTALLATION IS TO BE ADJUSTED TO OBTAIN TEMPERATURE RISE WITHIN THE RANGE SPECIFIED ON THE RATING PLATE.
• This chart is for information only. For satisfactory operation, external static pressure should not exceed value shown on the rating plate.
• The above chart is for U.S. furnaces installed at 0-2000 feet. At higher altitudes, a properly derated unit will have approximately the same
temperature rise at a particular CFM, while ESP at the CFM will be lower.
• Factory Motor Speed Setting: T1 = 1st Stage Ht, T2 = 2nd Stage Ht, T5 = Cooling.