Roubleshooting, Hart – Amana Gas Furnance S)8 User Manual

Page 39

Advertising
background image

39

T

ROUBLESHOOTING

C

HART

Associated

LED Code

2

2

LED Flash code will cease if power to the control module is interrupted through the disconnect or door switch.

• Induced draft blower runs

continuously. No furnace
operation.

• Integrated control module

diagnostic LED is flashing
continuously.

C

CONTINUOUS

• Polarity of 115

or 24 volt
power is
reversed.

• Polarity of 115 volt AC

power to furnace or

integrated control module

is reversed.

• Red and blue wires to

transformer are reversed.

• Poor unit ground.

• Review wiring diagram to

correct polarity.

• Verify proper ground.

Correct if necessary.

• Reverse red and blue

wires connected to
transformer.

• Turn power OFF

prior to repair.

• Normal operation.

• LED is steady on

STEADY

• Furnace not operating.

• Integrated control module

diagnostic LED is
flashing EIGHT (8)
flashes.

8 FLASHES

• Problem with

igniter circuit.

• Improperly connected

igniter.

• Bad igniter.

• Poor unit ground.
• Poor burner ground.

• Faulty integrated control

module.

• Check and correct wiring

from integrated control
module to igniter.

• Replace bad igniter.

• Check and correct unit

ground wiring.

• Replace bad integrated

control module.

• Turn power OFF

prior to repair.

• Replace igniter

with proper
replacement part.

• Read precautions

in “Electrostatic

Discharge”

section of manual.

Cautions

& Notes

Corrective Action

Possible Causes

Fault

Description(s)

Symptoms of

Abnormal Operation

FLASHING

Associated

LED Code

2