HP Netserver L Server series User Manual

Page 136

Advertising
background image

Appendix A

Specifications

130

Table A-2. Environmental Requirements

Parameter Conditions

Temperature
Operating

5

° to 35° C (41° to 95° F)

NOTE

• Subtract 1

°

C (2

°

F) from the maximum

temperature for each 609m (2,000 ft.) gain
above sea level
• Subtract 3

°

C (5

°

F) from the maximum

temperature if unit is installed in non-HP
enclosed cabinet

Non-operating

-40° to +65° C (-40° to +149° F)

Humidity

Operating

20% to 80% relative humidity,
non-condensing

Non-operating

5% to 95% relative humidity,
non-condensing

Altitude

Operating

-30 to 3,045 m (10,000 ft)

Non-operating

-30 to 12,180 m (40,000 ft)

Thermal Output

Maximum
Operating

1,365 BTU/hr

NOTE

The specifications and requirements listed above can vary if
you install a mass storage device in the HP Netserver that has
more stringent environmental limits than required for the
Netserver. Ensure the operating environment for any mass
storage devices you intend to install are compatible with the
Netserver’s environmental requirements.