Chapter 7

Rack Mounting the HP Netserver (4-Post)

64

Safety Precautions

Always keep the following safety and environmental issues in mind, especially if
you install the HP Netserver in a non-HP rack environment:

Optimum Operating Environment - The optimum operating conditions for

the HP Netserver is in an environmental controlled computer room with a
temperature range of 20 to 22

°C (68 to 72°F) at 40 to 60% relative humidity.

Maximum Ambient Temperature - Ensure the maximum ambient

temperature does not exceed 35

°C (95° F).

Elevated Operating Ambient Temperature - The ambient operating

temperature within a closed or multi-unit rack assembly is likely to exceed
the room's ambient temperature. Ensure the temperature within the rack itself
does not exceed 35

°C (95°F).

Reduced Air Flow - As you mount equipment in the rack, ensure you allow

enough air flow for safe operation of the equipment. The Netserver's fans
will only operate correctly if both front and rear doors of the rack allow free
air flow (perforated openings), or are removed.

Mechanical Loading - Uneven mechanical loading within the rack can cause

hazardous conditions. To prevent this in your installation plans, place the
heaviest components in the bottom of the rack, mounting all components as
low in the rack as is practical.

Circuit Overloading - Ensure the total configuration of equipment in the

rack does not overload the supply circuit. Check the nameplate ratings on all
equipment. Consider the effect of circuit overloading on overcurrent
protection and supply wiring.

Reliable Earth Grounding - Ensure rack-mounted equipment is reliably

grounded. Give particular attention to supply connections that are not direct
connections to the branch circuit (for example, use of non-HP power strips).