Chapter 3 _______________________________________________________________ Installation

VAISALA_______________________________________________________________________ 31

Power Supply Terminal Blocks

Conducting Off-Line Test

1.

Turn on the AC power to the wind sensor in your system (system
power distribution).

2.

Turn on the power switch in the power supply.

3.

Connect a laptop to the TEST connector in the power supply with
an RS-232 cable. Run the Diagnostics Program on the laptop.
Choose the option that connects the sensor to the laptop with the
system disconnected.

4.

Issue the WA command. The sensor must respond with a P status.

Table 1

Terminal Block 1

TB1
Terminal

Name

Description

1

12.6 V_H1

12.6 VAC transformer, line 1

2

12.6 V_CT

12.6 VAC transformer, center tap

3

12.6 V_H2

12.6 VAC transformer, line 2

4

36 V_H1A

24 VAC transformer, line A

5

36 V_H2A

24 VAC transformer, return A

6

36 V_H1B

24 VAC transformer, line B (internally connected to 36 V_H1A)

7

36 V_H2B

24 VAC tansformer, return B (internally connected to 36
V_H2A)

Table 2

Terminal Block 2

TB2
Terminal

Name

Description

1

TOP_HEAT

Top heater line, switched 24 VAC

2

ENCLOSUREHEATB

Two of two enclosure heater lines, switched 24 VAC

3

ENCLOSUREHEATA

One of two enclosure heater lines, switched 24 VAC

4

RETURN_36VAC_B

Heater return, ground at sensor

5

RETURN_36VAC_A

Heater return, ground at sensor

6

TOP_CTRL

To heater control, >+3 V = ON

7

ENLOSURE_CTRL

Enclosure heater control, >+3 V = ON

8

SENSOR+12V

+12 VDC to sensor

9

SENSOR_TXD

Connect to sensor TX data line

10

SENSOR_RXD

Connect to sensor RX data line

11

GND (12V Common)

Ground return from sensor

12

GND (RS232 Common) Connect to sensor cable shield