Second Analog Input Alarm

On models equipped with the Second Analog Input, the alarm(s) may be

configured to monitor the second input reading in addition to the main input.
Refer to the corresponding alarm operation figures for operation modes.

Note that deviation and band alarm modes are only valid for Internal

Cascade operation.

Absolute High Acting -2

(A2HI)

Absolute Low Acting -2

(A2LO)

Deviation High Acting -2

(d2HI)

ь

э

ю

Relative to SP-2, Second
Input (Internal Cascade)

Deviation Low Acting -2

(d2LO)

Band Inside Acting -2

(b2IN)

Band Outside Acting -2

(b2Ot)

Valve Fail Alarm (VFAL)

On models equipped with Valve Positioner (Position mode control only),

Alarm #1 may be configured as a valve fail alarm (Act1 = valv). This alarm
mode is useful to provide early detection of valve failure before significant
process errors occur. In this mode, the usual alarm function is disabled.

The alarm triggers under the two following conditions:

1. The valve slidewire feedback position does not match the controller output

power (within the valve position deadband) after the valve fail time has
expired. The alarm indicates that the valve cannot be properly positioned
due to a malfunction of the valve or valve positioner.

2. The slidewire feedback signal is broken or out of range. In this case, the

valve position controller cannot position the valve.

Message display alarms “valv” and “slid” appear when conditions 1 and 2

occur, respectively, whether or not the alarm is configured as a valve fail
alarm. This alarm mode also applies to linear DC output used for valve
positioning. In this case, a slidewire signal must be supplied to the controller
for valve fail detection. To silence a triggered Valve Fail alarm, see

Valve

Fail Time Alarm (VFAL) parameter, page 38.

The alarm action figures describe the status of the alarm output and the

front panel indicator for various over/under process conditions. (See

Output

Module “OUTPUT ON” State Table, page 6, for definitions, under installing
output modules section.) The alarm output wave form is shown with the
output in the automatic reset mode.

Note: Select the alarm action with care. In some configurations, the front panel

indicator (LED) might be “OFF” while the output is “ON”.