APPENDIX “B” - SPECIFICATIONS AND DIMENSIONS

1. DISPLAY: Dual 4-digit

Upper Process Display: 0.4" (10.2 mm) high red LED
Lower Auxiliary Display: 0.3" (7.6 mm) high green LED
Display Messages (Model dependent):

“OLOL”

– Appears when measurement exceeds + 105% input range.

“ULUL”

– Appears when measurement exceeds - 5% input range.

“SENS”

– Appears when measurement exceeds

±“OLOL” & “ULUL” range.

“....”

– Appears when display values exceed + display range.

“-...”

– Appears when display values exceed - display range.

“SLid”

– Appears when loss of slidewire signal is detected.

“VALV”

– Appears when valve actuator error is detected.

2. POWER: Switch selectable 115/230 VAC (+10%, -15%) no observable

line variation effect, 48-62 Hz, 10 VA.

3. ANNUNCIATORS:

LED Backlight Status Indicators (Model dependent):

%PW – Lower auxiliary display shows power output in (%).
DEV – Lower auxiliary display shows deviation (error) from setpoint.
OP1 – Main control output is active.
AL1

– Alarm #1 is active.

AL2

– Alarm #2 is active (for Dual Alarm Option).

OP2 – Secondary output is active (for Secondary Output Option).
OPN – Valve positioner OPEN output is active (for Valve Positioner option).
CLS

– Valve positioner CLOSE output is active (for Valve Positioner option).

SEC – Lower auxiliary display shows second analog input (for Second

Analog Input option).

MAN – Flashing: Controller is in Manual control mode.
REM – ON: controller is in remote setpoint mode (Second Analog Input option).

– OFF: controller is in local setpoint mode (Second Analog Input option).
– Flashing: controller is in Manual control mode

(Second Analog Input optional).

-69-

Figure 39, Dimensions

DIMENSIONS In inches (mm)

Note: Recommended minimum clearance (behind the panel) for panel latch installation is 5.5" (140)H x 2.1" (53.4)W.