Alarm reset (rst1, rst2) 32, Alarm standby delay (stb1, stb2) 32, Alarm value (al-1, al-2) 32 – Red Lion PCU User Manual

Page 40

Advertising
background image

Alarm Reset (rSt1, rSt2)

Each alarm reset action may be independently configured.

LAtC -

Latching

Auto -

Automatic

Latched alarms require operator acknowledgment to reset the alarm

condition. The front panel buttons can be used to reset an alarm when the
controller is in the hidden mode (see

Hidden Function Mode, page 20). An

Alarm condition may also be reset via the RS485 serial interface or by the user
input. Automatic (Auto) reset alarms are reset by the controller when the alarm
condition clears. Figure 16, Alarm Reset Sequence, depicts the reset types.

Alarm Standby Delay (Stb1, Stb2)

The alarm(s) may be independently configured to exhibit a power-on,

standby delay which suppresses the alarm output from turning “ON” until the
process first stabilizes outside the alarm region. After this condition is
satisfied, the alarm standby delay is canceled and the alarm triggers normally,
until the next controller power-on. Figure17, Alarm Standby Delay Sequence
depicts a typical operation sequence.

Alarm Value (AL-1, AL-2)

The alarm values are either absolute (absolute alarms) or relative to the

setpoint value (deviation and band alarms). An absolute alarm value is the
value that is entered. A relative alarm value is offset from the process setpoint
value by the amount entered and tracks the setpoint value as it is changed.

AL-1 and AL-2 -

-999 to 9999

If the alarm action is set as a Band Alarm, then only a positive value can be

entered.

AL-1 and AL-2 -

0 to 9999

-32-

Figure 16, Alarm Reset Sequence

Figure 17, Alarm Standby Delay Sequence

Advertising