Configure module 4 - alarms (4-al) 42 – Red Lion PCU User Manual

Page 50

Advertising
background image

Configure Module 4 - Alarms (4-AL)
Unit returns to configuration access point if alarm(s) are not
installed.

Display

Parameter

Range and Units

(Factory Setting Value)

Description/

Comments

Act1

Alarm 1 operation
mode

A-HI - absolute high
A-LO - absolute low
d-HI - deviation high
d-LO - deviation low
b-IN - band inside
b-ot - band outside
Valv - valve fail alarm
A2HI - absolute high,

second input

A2LO - absolute low,

second input

d2HI - deviation high,

second input, cascade

d2LO - deviation low,

second input, cascade

b2IN - band in, second

input, cascade

b2Ot - band out, second

input, cascade

(A-HI)

If changed, check
alarm values.

rSt1

Alarm 1 reset
mode

Auto - automatic
LAtc - manual reset
(Auto)

Manual reset via
hidden mode

Stb1

Alarm 1 standby
function (delay)

yes/no
(no)

Power-up
standby delay.

AL-1

Alarm 1 value

-999 to 9999
(0.0)

If band alarm
action, then only
a positive value
can be entered.

Display

Parameter

Range and Units

(Factory Setting Value)

Description/

Comments

Act2

Alarm 2
operation mode

A-HI - absolute high
A-LO - absolute low
d-HI - deviation high
d-LO - deviation low
b-IN - band inside
b-ot - band outside
A2HI - absolute high,

second input

A2LO - absolute low,

second input

d2HI - deviation high,

second input, cascade

d2LO - deviation low,

second input, cascade

b2IN - band in, second

input, cascade

b2Ot - band out, second

input, cascade

(A-HI)

If changed, check
alarm values.

rSt2

Alarm 2 reset
mode

Auto - automatic
LAtc - manual reset
(Auto)

Manual reset via
hidden mode.

Stb2

Alarm 2 standby
function (delay)

yes/no
(no)

Power-up standby
delay.

AL-2

Alarm 2 value

-999 to 9999
(0.0)

If band alarm
action, then only a
positive value can
be entered.

AHYS

Alarm Hysteresis
value

1 to 250
(0.1)

Applies to both
alarms. Set to
eliminate chatter.

-42-