Configure module 1 - input parameters (1-in) 39 – Red Lion PCU User Manual

Page 47

Advertising
background image

REFERENCE TABLES: CONFIGURATION PARAMETER
MODULES

Configure Module 1 - Input Parameters (1-IN)

Display

Parameter

Range and Units

(Factory Setting

Value)

Description/

Comments

tYPE

Input type

VOLt - Voltage

Curr - Current
(Curr)

root

Square root
linearization

Yes/no
(no)

Second Analog Input
Models only.

dCPt

Decimal
point

0, 0.0, 0.00, or 0.000
(0.0)

If 0.000 is selected,
scaling points must
be a positive value.

rnd

Rounding
increments

1, 2, 5, 10, 50, or 100
(0.1)

Used in conjunction
with filtering to
stabilize the display
reading.

FLtr

Digital
filtering for
input signal

0 to 4
(1)

Increase number for
more filtering effect.
4 = 2/sec display
update rate.

dSP1

Scaling point

#1 Display

Value

-999 to 9999
(0.0)

Normally, key-in
display low value.

INP1

Scaling point
#1 input
signal value
key-in method

-999 to 9999
(4.00)

Normally, key-in input
low value. Press DSP
button to select signal
input method.

Signal input
method

4 to 20 mA
0-10 VDC

0.00 to 20.00
0.00 to 10.00

Normally, apply input
low value.

dSP2

Scaling point
#2 display
value

-999 to 9999
(100.0)

Normally, key-in
display high value.

Display

Parameter

Range and Units

(Factory Setting

Value)

Description/

Comments

INP2

Scaling point
#2 input
signal value
key-in method

-999 to 9999
(20.00)

Normally, key-in input
high value. Press
DSP button to select
signal input method.

Signal input
method

4 to 20 mA

0-10 VDC

0.00 to 20.00
0.00 to 10.00

Normally, apply input
high value.

SPLO

Lower limit
setpoint range

-999 to 9999
(0.0)

Set low limit below
high limit.

SPHI

Upper limit
setpoint range

-999 to 9999
(999.9)

Set high limit above
low limit.

SPrP

Setpoint ramp
rate

0.0 to 999.9
units/minute
(0.0)

0.0 is off (no ramping)
This parameter also
ramps Remote
Setpoint.

InPt

User input

PLOC - Program

disable

ILOC - Integral action

on/off

trnf - auto/manual

select

SPrP - Setpoint ramp

rate on/off

ALrS - Reset alarm

output(s)

Prnt - print request
SPSL - Remote/Local

Setpoint select

(PLOC)

Available on all
second input ( MVP
and ANA) models and
on models with
RS485.

-39-