Output status 48 – Red Lion PCU User Manual

Page 56

Advertising
background image

SENDING COMMANDS AND DATA (Cont’d)

VALUE

IDENTIFIER

DESCRIPTION

SERIAL

MNEMONIC

UNITS

A

Input Display Value

INP

U

B

Setpoint

SET

U

C

Output Power

PWR

%

D

Proportional Band

PBD

%

E

Integral Time

INT

S

F

Derivative Time

DER

S

G

Alarm 1

AL1

U

H

Alarm 2

AL2

U

I

Deviation

DEV

U

J

Output Power Offset

OFP

%

K

Setpoint Ramp Rate

RMP

R

L

Relative Gain

CRG

G

M

Deadband

CDB

U

O

Remote Setpoint Ratio

RAT

R

Q

Remote Setpoint Bias

BIA

U

S

Controller Mode

1 -Automatic
2 - Manual
(User)

U

Setpoint Mode

1 – Local
2 - Remote

W

Output status*

OST

U

X

Secondary Proportional Band

PB2

%

Y

Secondary Integral Time

IT2

S

Z

Secondary Derivative Time

DT2

S

AA

Second Input Reading

IN2

U

BB

Remote Setpoint Reading or
Secondary Directed Setpoint

RSP or
SP2

U

Output status transmission format = ABCD (0 = output off, 1 = output on)

Note: The % output power can be changed only if the controller is in the manual

mode of operation.

* The output status indicates the status of the controller’s outputs. The status can

only be read (see the following table). The alarms outputs may be reset by the

reset operator(R).

Output Status

NON-VALVE POSITIONER MODELS

VALVE POSITIONER MODELS

A = Main output (OP1)

A

=

Alarm 1 output(AL1)

B = Secondary output (OP2)

B

=

0

C = Alarm 2 output (AL2)

C

=

Motor close output(CLS)

D = Alarm 1 output (AL1)

D

=

Motor open output(OPN)

Example:

OP1 = ON, OP2 = OFF, AL2 = OFF, AL1 = ON
Transmission = “ OST 1001”

Note: The % output power can be changed only if the controller is in the

manual mode of operation.
The command string is constructed by using a command, a value

identifier, and a data value if required. The Data value need not contain the
decimal point since it is fixed within the unit, when programmed at the
front panel. The PCU accepts the decimal point, however it does not
interpret them in any way. Leading zeros can be eliminated, but all trailing
zeros must be present.

Example: If an alarm value of 750.0 is to be sent, the data value can be

transmitted as 750.0 or 7500. If a 750 is transmitted, the alarm value
changes to 75.0 in the unit.
The address command allows a transmission string to be directed to a
specific unit on the serial communications line. When the unit address is
z e r o , t r a n s m i s s i o n o f t h e a d d r e s s c o m m a n d i s n o t r e q u i r e d . F o r
applications that require several units, it is recommended that each unit on
the line be assigned a specific address.
If they are assigned the same address, a Transmit Value Command causes
all the units to respond simultaneously, resulting in a communication
collision. The command string is constructed in a specific logical
sequence. The PCU does not accept command strings that do not follow
this sequence. Only one operation can be performed per command string.

-48-