Second analog input calibration (2cal) 80, Second analog input (remote setpoint) 80, Motorized valve positioner 80 – Red Lion PCU User Manual

Page 88

Advertising
background image

Second Analog Input Calibration (2CAL)

The signals applied to the Second Analog Input for calibration depend on

the type of model. Second Analog Input and Motorized Valve Positioner
represent the models for which unique calibration signals are required.

Second Analog Input (Remote Setpoint)

Connect precision DC milliampere source (0.01% accuracy) to rear

terminals labeled Second Analog Input, 4 to 20 mA+ and 4 to 20 mA-.

Display

Parameter

Description/Comments

StP1

0.00 mA step

Apply 0.00 mA DC, press PAR.

StP2

5.00 mA step

Apply 5.00 mA DC, press PAR.

StP3

10.00 mA step

Apply 10.00 mA DC, press PAR.

StP4

15.00 mA step

Apply 15.00 mA DC, press PAR.

StP5

20.00 mA step

Apply 20.00 mA DC, press PAR.

Motorized Valve Positioner

Construct a precision resistor

divider network consisting of
f o u r 2 5 0

W 0.1% tolerance

resistors connected in series as
shown in Figure 43, Resistor
Divider. Connect one end of the
r e s i s t o r s t r i n g t o t h e r e a r
t e r m i n a l l a b e l e d S l i d e w i r e
Feedback Inputs, Comm. and the
other end to Excitation. The
connection to the Wiper terminal
comes from different points of
the resistor string.

Display

Parameter

Description/Comments

StP1

0.0% step

Connect wiper input to 0% point of divider
(Comm.), wait 10 seconds, press PAR.

StP2

25.0% step

Connect wiper input to 25% point of divider, wait
10 seconds, press PAR.

StP3

50.0% step

Connect wiper input to 50% point of divider, wait
10 seconds, press PAR.

StP4

75.0% step

Connect wiper input to 75% point of divider, wait
10 seconds, press PAR.

StP5

100.0% step

Connect wiper input to 100% point of divider
(Excitation), wait 10 seconds press PAR.

-80-

Figure 43, Resistor Divider