Configure Module 7 - Second Analog Input (7-2N)
Unit returns to configuration access point if Second Analog Input option
is not installed.

Display

Parameter

Range and Units

(Factory Setting

Value)

Description/

Comments

OPEr

Second Analog
Input operation
mode

CSCd - Internal

Cascade mode

rSP - Remote

Setpoint mode

(rSP)

Remote Setpoint
mode also for
External Cascade

root

Square root
linearization

yes/no
(no)

Linearization applies
to the Second Input

dPt2

Second Input
decimal point
position

0, 0.0, 0.00
or 0.000
(0.0)

Normally same
position as main
input for Remote
Setpoint

dSP1

Second Input
scaling point #1
display value

-999 to 9999
(0.0)

Normally key-in
process low value

INP1

Second input
scaling point #1
input value

-9.99 to 99.99
(4.00)

Either key-in value
or press DSP for
measure/record
mode

dSP2

Second Input
scaling point #2
display value

-999 to 9999
(100.0)

Normally key-in
process high value

INP2

Second input
scaling point #2
input value

-9.99 to 99.99
(20.00)

Either key-in value
or press DSP for
measure/record
mode

SPtr

Local/Remote
Setpoint transfer
action

nor - normal
Auto - automatic
trAC - track
(nor)

Applies only to
Remote Setpoint
mode.

OPd2

Secondary output
power dampening

0 to 250 seconds
(2)

0=off

Configure Module 8 - Valve Positioner (8-VP)
Unit returns to configuration access point if Valve Positioner option is
not installed.

Display

Parameter

Range and Units

(Factory Setting

Value)

Description/

Comments

VPS1

Valve position #1

-99.9 to 999.9%
(0.0)

Normally full closed
valve position.
Either key-in value or
press DSP for
measure/record mode

VPS2

Valve position #2

-99.9 to 999.9%
(100.0)

Normally full open
valve position.
Either key-in value or
press DSP for
measure/record mode

VUdt

Valve update time

0 to 250 seconds
(10)

0 = update at a rate of
10/sec.

VPdb

Valve position
deadband

0.1 to 25.0%
(2.5)

Adjust to reduce
hunting and valve
activity (Position
mode only)

VFAL

Valve fail time
alarm

0 to 9999 seconds
(0)

0=off, set value larger
than update time plus
motor transit time
(Position mode only)

VOPt

Valve motor open
time

1 to 9999 seconds
(30)

Measure actual valve
motor open time
(Velocity mode only)

VCLt

Valve motor close
time

1 to 9999 seconds
(30)

Measure actual valve
motor close time
(Velocity mode only)

VOnt

Valve minimum on
time

0.1 to 25.0 seconds
(1.0)

Adjust to reduce
hunting and valve
activity (Velocity
mode only)

-45-