2 limit value curve, 2 limit value curve -31, Operating instructions arimetec – ARI Armaturen ARImetec-S EN User Manual

Page 31

Advertising
background image

Rev. 0040807015 1014

Page 2-31

Operating Instructions

ARImetec

®

-S

7.1.2 Limit value curve
Evaluation of steam trap surface temperatures:

Fig. 6

Leaking !

Te

mperature in °C / st

ructure-borne sound level

p in bar(ü)

A measurement with headphones is recommended

at low steam pressures in order to obtain a clear

result.

Borderline

Steam trap OK acc. to

temperature measurement

Cold or blocked

Steam trap OK acc. to

ultrasonic measurement

Temp. measurement

Limit value curve

for ultrasound

Lower limit temperature

Surface t

min external

°C

Surface t

external

°C

Upper limit temperature for

thermostatic steam traps
Surface t

max external

°C

Limit value for ultrasound

Advertising