Balboa Water Group BP 50Hz User Manual

Page 17

Advertising
background image

17

Manufactured under one or more of these patents. U.S. Patents: 5332944, 5361215, 5550753, 5559720, 5,883,459, 6253227, 6282370, 6590188, 6976052, 6965815, 7030343, 7,417, 834 b2,

Canadian Patent: 2342614, Australian patent: 2373248 other patents both foreign and domestic applied for and pending. All material copyright of Balboa Water Group.

42217B

Two Pole RCD

Four Pole RCD

A residual current device (RCD,) is the generic term for a
device that monitors the current in the line conductor and the
neutral conductor of a circuit in an earthed system.

In a circuit that’s operating properly, the vector sum of the
live and neutral current values added together will be zero.
Current flowing to earth, due to a line earth fault, will return
via the earth conductor, and regardless of load conditions,
will be registered as a fault. This current flow will give rise to
a residual current that will be detected by the device. If the
residual current exceeds the rated sensitivity of the RCD, it
will automatically activate a tripping of the faulty circuit.

Typical specifications are as follows:

Residual Current Devices ( RCD’s ) range
Sensitivity - from 10 to 500mA
Voltage - 2 poles : 230V; 3/4 poles: 230/400V
Connection capacity
- 25A: 6/10 mm² (flexible/ rigid cable)
- 40,60A: 16/25 mm²
- 80,100A: 35/50 mm²

230 Volt 50 Hz - Residual Current Devices (RCD’s)

Advertising