Wiring check for rcd and service disconnect – Balboa Water Group BP 50Hz User Manual

Page 19

Advertising
background image

19

Manufactured under one or more of these patents. U.S. Patents: 5332944, 5361215, 5550753, 5559720, 5,883,459, 6253227, 6282370, 6590188, 6976052, 6965815, 7030343, 7,417, 834 b2,

Canadian Patent: 2342614, Australian patent: 2373248 other patents both foreign and domestic applied for and pending. All material copyright of Balboa Water Group.

42217B

IMPORTANT!

Remember, high voltage is still accessible in the house breaker
box even though you have turned off the spa breaker.
Keep in mind that a majority of R.C.D. tripping problems can be
attributed to incorrect wiring. R.C.D. troubleshooting usually
finds the problem.

RCD LINE-IN WIRING CHECK

UÊ œV>ÌiÊ̅iК«Аœ«iÀÊVˆÀVՈÌÊLÀi>ŽiÀÊ>˜`КМХА˜КˆМКœvv°
UÊ ,i“œÛiÊ̅iÊVœÛiÀÊvÀœ“Ê̅iʅœÕÃiÊLÀi>ŽiÀÊLœЭ°К …iVŽ

the main service amperage rating to the breaker box.

UК Аœ“КМ…iКVˆАVХˆÌÊLÀi>ŽiА]КœV>ÌiÊ̅iÊLÀœЬ˜Кœ>`Ê܈ÀiÊ>˜`Ê̅iÊ

blue neutral wire.

UК Аœ“КМ…iК,° ° °К˜iÕÌÀ>ÊL>А]КœV>ÌiÊ̅iÊLÕiʏœ>`ʘiÕÌÀ>]Ê>˜`Ê

the green ground wire.

UÊ iÊÃÕÀiÊ̅iÀiÊ>АiʘœКœМ…iАК>««ˆ>˜ViÃʜ˜Ê̅iÊë>Ê

circuit. If there are, service must be re-wired to supply the
spa only.

UÊ >ŽiÊÃÕÀiÊ>Ê̅ÀiiÊ܈ÀiÃÊi݈ÌÊ̅iʅœÕÃiÊLÀi>ŽiÀÊLœÝÊۈ>Ê

conduit, routed to the R.C.D. breaker box. The brown should
be connected to the R.C.D. line-in. The blue load neutral con-
nects to the neutral in.

RCD LINE-OUT WIRING CHECK FOR 230 V DEDICATED
SYSTEM

The brown wire should connect to load out, the blue wire from
neutral out. All wires will exit the box via conduit routed to the
spa control system.

Once you have found all wiring correctly installed, begin
to check for proper voltage. If Correct Wiring is Verified,
check to see if the proper RCD is installed.

Check the label in the system box near TB1 to determine the

maximum amperage draw for the system.
Be sure the R.C.D. is rated for more amperage than the

system will draw.
For a 230 V dedicated system, a 2-pole or 4-pole R.C.D. with

no load neutral is acceptable.
For a detailed wiring checklist, please review the previous

segment of this manual on proper R.C.D. wiring or the R.C.D.
manufacturer’s instructions.
If the wiring is correct and the R.C.D. will not reset, then

unplug the pump and try to reset the R.C.D.
If the R.C.D. trips again, then unplug the blower and push

the reset button. If the R.C.D. continues to trip, then do the
same procedure for the ozone generator.
If the R.C.D. stops tripping after you unplugged one of the

spa’s components, turn off the power to the spa then plug in
each component except the one that tripped the R.C.D.
Power up the system. If the R.C.D. no longer trips, then you

have correctly identified the problem.
Repair or replace the component as instructed by the spa

manufacturer.
If you have unplugged all of the spa’s components and the

R.C.D. still doesn’t reset, then the problem is most likely a
ground fault in the heater.
Disconnect the heater, and test.

Wiring Check for RCD and Service Disconnect