Recommendations for installation – NOVUS V1.5x A User Manual

Page 10

Advertising
background image

NOVUS AUTOMATION

www.fieldlogger.net

10/103

Fig. 12 - FieldLogger front panel

FieldLogger has two rows of terminals for diverse connections; among them are the following items: Ethernet, input
connections, power supply, output relays, auxiliary power supply output, digital inputs and serial communication. This
information is identified in the box of FieldLogger according to Fig. 13 and Fig. 14:

Fig. 13 - Upper side connections for standard and 24 V models

NOTES:

1) An external protection device consisting of a 0.5 A slow blow fuse (UL Listed) must be wired near to the

FieldLogger

.

2) A switch or circuit-breaker placed near to the

FieldLogger

shall be used as the disconnecting device.

Fig. 14 - Lower side connections

RECOMMENDATIONS FOR INSTALLATION
• Input signal leads must be installed in grounded conduits and away from power or contactor wires.
• Instruments must be powered only by an exclusive power supply.
• Installing RC filters (47 Ω and 100 nF, serial) is strongly recommended at contactor coils or any other inductors.
• System failure should always be taken into account when designing a control panel to avoid irreversible damage to

equipment or injury to people. The RL1 and RL2 output relays, used as alarms, do not warrant total protection.

• Wires section: minimum gauge 0.14 mm².

Advertising