VERTICAL, THROUgH THE ROOF

INSTALLATION

• For a typical Vertical Through the Roof

installation, refer to Figures 5 and 6.

Terminate the system 6’ (1.8m) from the

combustion air intake of any appliance.

•Terminate the system at least 3’ (.9m) from

any other building opening, gas utility meter,

service regulator or the like.

•Terminate the system at least 2’ (.61m) above

the roof line and any wall or vertical structure

closer than 8’ (2.4m). Additional support is

required for systems that extend more than 6’

(1.8m) above the roof line.

•Enclose residential exterior vent systems

below the roof line or use FasNSeal® W2

to limit condensation and protect against

mechanical failure.

•Install a Wall Bracket after every transition

from horizontal to a vertical run of over 10’

(3.05m), a minimum of every 12’ (3.66m) of

vertical run, and after any offset in the vertical

run. (See Detailed FNS® Wall

Bracket Installation)

•Unless FasNSeal® is installed in a fire rated

shaft, a fire stop and support is required

when penetrating through each floor/ceiling

level (See Figure 5). A Firestop is not needed

at the roof level.

•The total equivalent vent length from

appliance flue collar to the termination shall

not be greater than specified in the appliance

manufacturer’s installation instructions.

•A FasNSeal® Rain Cap or any other provision

as required by the appliance manufacturer

must be used to keep rain or debris out of the

vent.

1. Locate the path for the vent system.

2. Cut and frame openings in floors and

ceilings to accommodate Firestops.

3. Cut the opening in the roof for the Roof

jack. Cut the opening so that a minimum

distance of 1”/25.4 mm is between the Roof

Vertical Termination

Figure 6

Vertical Through the

Roof Installation

RAINCAP

ADjUSTABLE

FLASHING

SUPPORT

CLAMP

FIRESTOP

HORIZONTAL

DRAIN TEE OR

DRAIN FITTING

W/TEE

TO DRAIN. DISPOSE OF

CONDENSATES ACCORDING TO

LOCAL CODES

APPLIANCE

STORM COLLAR

APPLIANCE

ADAPTER

HANGER

STRAP

Figure 5

FIRESTOP

FLAT TO 9/12

VARIABLE

PITCH

FLASHING

ROOF jACK

VENT LENGTH

1.0”

0.5”

STORM COLLAR