Wall thimble installation, Figure 4 – DuraVent FasNSeal Single-Wall User Manual

Page 9

Advertising
background image

Wall Thimble Installation

OUTSIDE

BUILDING

SURFACE

INSIDE

BUILDING

SURFACE

PART B

PART A

TO TERMINATION

TO APPLIANCE

9.0” + 3.0”

1.5”

1.0”

2” x 6” STUD
(COMBUSTIBLES)

9

Category II, III, or IV appliances) of no less

than 1/4” (6.4mm) every 12” (305mm) to

prevent collection of condensates, formation

of ice build up, or blockage at any location

within the assembly. Refer to appliance

manufacturer’s installation instructions for

further details regarding the installation of

condensate drain fittings and the pitch

of the system.

•Use non-combustible hanger straps a

minimum of every 6’ (1.8m) to support the

vent system from ceiling joints or other solid

structures. Do not puncture the vent system!

1. Determine the location and install the

Wall Thimble so that a continuous minimum

slope of 1/4” per foot is maintained in any

horizontal portion of the vent system.

Condensate must flow freely and may not

be retained in any part of the vent system.

2. Cut the opening for the Wall Thimble

to allow the spacer tabs protruding from

the outer plate to sit comfortably within

the opening. (See Figure 4, Wall Thimble

Installation diagram)

3. Position Part A into the opening so that the

gasketed end of the Wall Thimble is located

on the outside of the structure.

Figure 4

4. Apply a bead of silicone between the two

surfaces and around the edges before nailing

or screwing the plate on Part A to the outside

of the structure.

5. From the inside, slide the sleeve of Part B

onto the sleeve of Part A until Part B’s plate

is flush against the inside structure surface.

Fasten with screws or nails.

IMPORTANT

6. Use a Termination Tee or a Birdscreen to

finish the system’s exterior.

7. When the vent system must pass through

an interior wall, use a FasNSeal Wall Pass

Through (FSWPT). Cut the same size hole for

the FSWPT as was cut for the Wall Thimble

and install using the same method.

8. Assemble FasNSeal® from the appliance

towards the Wall Thimble. Refer to “joint

Connections” in these installation instructions

for procedure.

Do not drill through or penetrate any part

of the vent system.

When terminating through a

non-combustible wall, the wall thimble

is optional.