General termination guidelines – DuraVent FasNSeal Single-Wall User Manual

Page 17

Advertising
background image

17

• Proper clearances to combustibles must

be maintained over the entire length of the

system (refer to Figure 17).

• Never install FNS on an appliance that is not

listed for use with a Special Gas Vent or Type

BH vent.

• Additional FNS vent lengths can be

installed for extended runs. The overall

equivalent length of the system shall not

exceed the specifications of the appliance

manufacturer’s instructions.

• Horizontal vent runs shall have a slope of

no less than ¼ inch (6.4mm) every 12 inches

(305mm) to prevent collection

of condensates.

• The termination should be away from trees,

shrubs, or decorative items as flue gases

could cause damage.

• The venting system must be free to expand

and contract.

• Check for unrestricted vent movement

through walls, ceilings, and roof penetrations.

• Different Manufacturers Have Different joint

Systems and Adhesives. Do Not Mix Pipe,

Fittings, or joining Methods from

Different Manufacturers.

• Clearances must be increased in

applications exceeding 400 degree

outlet temperatures.

gENERAL TERMINATION

gUIDELINES:

NOTICE: The following is to be used as a

guideline only.

Check with the Code enforcement office

in your area forspecific termination

requirements. A mechanical draft vent

system, excluding direct-vent appliances,

shall terminate at least 4 feet (1219 mm)

below, 4 feet (1219 mm) horizontally from,

or 1 foot (305 mm) above any door, window,

or gravity air inlet into any building. The

bottom of the vent terminal shall be located

at least 12 inches (305 mm) above grade. In

geographical areas where snow accumulates,

terminate the system at least 12 inches above

the snow line. The termination must be kept

clear of snow and ice at all times. Do not

terminate over public walkways or over an

area where condensate or vapor could create

a nuisance or hazard or could be detrimental

to the operation of regulators, relief valves, or

other equipment.

Advertising