Horizontal, through the wall installation, Horizontal through-the-wall installation, Figure 3 – DuraVent FasNSeal Single-Wall User Manual

Page 8

Advertising
background image

Horizontal Through-The-Wall Installation

TERMINATION TEE OR

BIRD SCREEN

6’ MAx.

HORIZONTAL DRAIN TEE

OR DRAIN FITTING WITH TEE

HANGER STRAP

WALL THIMBLE

TO DRAIN DISPOSE
OF CONDENSATE
ACCORDING TO
LOCAL CODES

APPLIANCE ADAPTER

APPLIANCE

ELBOW

8

HORIzONTAL, THROUgH THE

WALL INSTALLATION

• For a typical Horizontal Through the Wall

installation, refer to Figure 3. When venting

through a sidewall, terminate the system not

less than 12” (.3m) above the ground and

above the snow line in geographical areas

where snow accumulates. The termination

area must be kept clear of snow and ice

at all times.

•Terminate the system at least 7’ (2.1m) above

a public walkway or driveway, no less than

6’ (1.8m) from the combustion air intake

of any appliance or 3’ (.9m) from any other

building opening, gas utility meter, service

regulator or the like. It also shall terminate

at least 3’ (.9m) above any forced air inlet

within 10’ (3.1m) and shall terminate at least

4’ (1.2m) below, 4’ horizontally from or 1’

(.3m) above any door, window, or gravity

air inlet into any building as provided in the

National Fuel Gas Code ANSI Z223.1/NFPA

54 or the International Fuel Gas Code. Proper

judgement may require greater distances

depending on the size of the equipment

installed or to allow for snow drifting or

falling from overhead roofs or trees. The

termination should be far enough away from

trees, shrubs or decorative items to

prevent damage.

•The total vent length from the appliance flue

collar to the outside termination shall not

be greater than specified in the appliance

manufacturer’s instructions.

•A horizontal installation shall have a slope

(upwards away from the appliance for

Figure 3