4. Cut off the remaining foam insulation.

5. If necessary, bend the pipe to fit along the bottom of the indoor unit.

Then pull it out through the appropriate hole.

The pipe should not project from the rear of the indoor unit.

The bending radius should be 3.94inch(100 mm) or more.

6. Pass the pipe through the hole in the wall.

7. For further details on how to connect to the outdoor unit and purge the air, refer to page 35~37.

• Tighten the flare nut with torque wrench according to specified method.

If the flare nut is over-tightened, the flare may break and cause refrigerant gas leakage.

• DO NOT WALL UP THE PIPE CONNECTION !

All refrigerant pipe connection must be easy accessible and serviceable.

• The pipe will be insulated and fixed permanently into position after finishing the installation and the gas leak test;

refer to page 38 for further details.

1. Unscrew the caps at the end of each pipe.

All inert gas exhausts from the indoor unit.

The indoor unit is supplied with inert gas (nitrogen).
Before installing the unit, check if nitrogen gas flow out of indoor unit.
If this one isn’t true, DO NOT INSTALL THE UNIT since leakage could be inside the indoor unit.

A 24.6ft(7.5m) pipe is supplied with the air conditioner.

The length of the pipe can be:
• Extended up to : see table page 24
• Shorten up to: see page 24

If you need a pipe longer than 24.6ft(7.5m):
• You must extend the assembly cable.
• You must add refrigerant to the pipes; otherwise, the indoor unit may freeze.

Unscrew the caps

Pipes

• The remaining air in the Refrigeration cycle, which contains moisture,

may cause malfunction on the compressor.

• Always contact the service center or a professional installation agency

for product installation.

• To prevent dirt or foreign substances from getting into the pipes during

installation, do NOT remove the caps completely until you are ready to

connect the pipes.

Cutting or extending the pipe

Purging the indoor unit