Cutting or extending the pipe – Sunlight Supply Samsung Linesets for Mini Split Systems User Manual

Page 32

Advertising
background image

32

Cutting or extending the pipe

Outer Diameter

Torque

ø1/4inch(6.35mm)

10.1~12.3 ft.lb (140~170 kgf.cm)

ø3/8inch(9.52mm)

18.1~20.3 ft.lb (250~280 kgf.cm)

ø1/2inch(12.70mm)

27.5~30.4 ft.lb (380~420 kgf.cm)

ø5/8inch(15.88mm)

31.8~34.7 ft.lb (440~480 kgf.cm)

ø3/4inch(19.05mm)

71.6~87.5 ft.lb (990~1210 kgf.cm)

ø7/8 inch(22.23mm)

71.6~87.5 ft.lb (990~1210 kgf.cm)

Indoor outlet pipe

Connecting pipe

Flare nut

5. Check if you flared the pipe correctly (see examples of incorrectly flared pipes below).

6. Align the pipes to connect them easily. Tighten the flare nuts first with your hands, and then with a torque wrench,

applying the following torque:

7. For further details on how to connect to the outdoor unit and purge the air, refer to page 35~37.

Correct

Uneven

Thickness

Cracked

Damaged

Surface

Inclined

• Excessive torque can be cause of gas leakage. In case brazing the pipe, the nitrogen gas must be blown into the

pipe (50 Pa). The joint must be accessible and serviceable.

• Tighten the flare nut with torque wrench according to specified method.

If the flare nut is over-tightened, the flare may break and cause refrigerant gas leakage.

1. Make sure that you have all the required tools (pipe cutter, reamer, flaring tool and pipe holder).

2. If you want to shorten the pipe, cut it using a pipe cutter, ensuring that the cut edge remains at 90° with the side of the

pipe (see below examples of correct and incorrect cut edges).

3. To prevent a gas leak, remove all burrs at the cut edge of the pipe using a reamer.

4. Put a flare nut slightly into the pipe and modify the flare.

Oblique

Rough

Burr

Pipe

cutter

Pipe

Outer Diameter (D)

Depth (A)

Flaring Size (B)

ø1/4inch(6.35mm) 0.051inch(1.3mm) 0.354inch(9.0mm)
ø3/8inch(9.52mm) 0.071inch(1.8mm) 0.512inch(13.0mm)

ø1/2inch(12.70mm) 0.079inch(2.0mm) 0.638inch(16.2mm)
ø5/8inch(15.88mm) 0.087inch(2.2mm) 0.760inch(19.3mm)
ø3/4inch(19.05mm) 0.087inch(2.2mm) 0.886inch(22.5mm)

ø7/8 inch(22.23mm) 0.087inch(2.2mm) 1.012inch(25.7mm)

Pipe

Flare

• Face the pipe down while removing the burrs to make sure that burrs do not get in to the pipe.

Vivaldi MAX_AQN09VFU@@ IB&IM_32163A_E.indd 32

2012-6-20 13:29:00

Advertising