CONDENSATE &

PRESSURE RELIEF PIPEWORK

INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32
8 716 113 389b (09/07)

12

P

R

E -

IN

ST

AL

LA

TI

O

N

CONDENSATE &

PRESSURE RELIEF PIPEWORK

CONDENSATE PIPEWORK:

• All national and, where appropriate, local

regulations for the discharge and
neutralisation of condensate should be
followed.

• The condensate pipe must be a minimum of

21.5mmØ polypropylene pipe.

• The condensate pipework must fall at least

50mm per metre towards the outlet and
should take the shortest practicable route
and not exceed 3 metres outside the building.
If a run greater than 3m is required, 32mmØ
polypropylene pipe must be used.

• The pipework must follow one of the options

shown opposite:

a - Internal waste drainage system

b - Soil/vent stack

c - External drainage system

d - External condensate absorption point

• Condensate pipework must not be connected

to rainwater downpipes.

• Use waterproof pipe insulation in exposed

positions and for external pipework

IMPORTANT: Condensate pipework must not
leak and the condensate trap must be filled
with water before the boiler is started to
prevent the possibility of potentially harmful flue
products escaping via the condensate route.

A - Condensate from the boiler condensate

trap (supplied) which has a 75mm
minimum water seal.

B - Sink.

C - 21.5mm Ø polypropylene condensate pipe.

D - Gully.

E -

Internal soil and vent stack.

F -

300mm x 100mm Ø sealed plastic tube.

G - Ground level.

H - Drainage holes 50mm from base of tube

(12mm Ø at 25mm centres) facing away
from building.

I -

Limestone chippings.

PRESSURE RELIEF PIPEWORK:

IMPORTANT: The pressure relief valve is a
safety device for the boiler and if activated may
discharge boiling water or steam through the
relief valve drain pipe.
Care should be taken when siting the outlet
pipe so that it does not cause an obstruction or
discharge above a window, entrance or other
public access where it could cause a hazard.

• The pressure relief drain pipe (K) should be

at least 15mm diameter copper pipe and run
downwards away from the boiler and discharge
away from any electrics or other hazard,
preferably to an external drain or soakaway.

• Pipe (K) should be finished with a partial

bend, near the outlet to face the external
boiler casing (as shown) to help prevent
freezing.

J -

External boiler casing.

K -

Pressure relief pipe.