Fault finding – Bosch 25/32kW User Manual

Page 45

Advertising
background image

PROBLEM

CAUSE

REMEDY

LOCKOUT:

Pulsation on start

Combustion settings incorrect

Set up as in installation instructions

Faulty nozzle

Replace nozzle

Intermittent lockout

Bad electrical connection

Check control box/electrical connections

Intermittent flame detection fault

See flame detection fault

Burner motor fails to
operate

Faulty motor or electrical supply
to motor

Check for 230v at motor plug during
startup period

Control box fault

Replace control box

Flame detection

Photocell filmed over (dirty)

Wipe clean

fault

Photocell faulty

Replace

Control box faulty

Replace

Incorrect CO

2

Air adjustment fault

Set up as in installation instructions

Oil pressure incorrect

Set up as in installation instructions

No oil from nozzle

No oil at pump

Check and refill oil tank/bleed oil line

Check and clean filters & valves from oil
tank to boiler

Air in pump

Bleed pump

Nozzle blocked

Replace nozzle

Faulty pump or drive

Replace

Faulty mechanical shut off valve

Clean or replace

(12/18 & 18/25 only)

Ignition failure

Electrode settings incorrect

Set up as in installation instructions

Faulty ignition transformer

Replace

Open circuit ignition

Check and replace electrodes or high
tension leads if necessary

Faulty control box or electrical
connections not properly made

Correct control box electrical
connections or replace control box

BURNER FAILS

No power to boiler

Check electrical / control circuit

TO START

Faulty boiler thermostat

Check by temporarily linking out high
limit and control thermostats

Programmer open circuit

Check by temporarily linking 8 & 9 on
the connector

Faulty control box

Replace

HIGH SMOKE

Air intake/flue blocked

Check & clear air intake/flue

NUMBER

Incorrect combustion settings

Set up as in installation instructions

Oil pressure incorrect

Adjust to correct pressure

Incorrect components used on
combustion head

Check with installation instructions

Faulty nozzle

Replace nozzle

FAULT FINDING

INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32
8 716 106 252b (07/06

44

FA

U

LT

F

IN

D

IN

G

& D

IA

G

R

A

M

S

FAULT FINDING

BOILER LOCKOUT :
Indicated by the illumination of the 'Lockout'
indicator on the fascia.
To reset, wait 2 minutes then press the lockout
reset button.

Also refer to fault finding logic on pages
46 and 47.

UNDER NO CIRCUMSTANCES MUST AN
APPLIANCE BE LEFT TO OPERATE WITH
ANY CONTOL LINKED OUT OR
OVERRIDDEN.