General checks, Boiler runs straight to lockout, No domestic hot water (external programmer) – Bosch 25/32kW User Manual

Page 52: No central heating (external programmer)

Advertising
background image

CONTACT INFORMATION

WORCESTER, BOSCH GROUP:

TECHNICAL:

08705 266241

SERVICE:

08457 256206

SPARES:

01905 752571

LITERATURE:

01905 752556

TRAINING:

01905 752526

SALES:

01905 752640

WEBSITE:

www.worcester-bosch.co.uk

WATER TREATMENT:

FERNOX

01799 550811

www.fernox.com

SENTINEL 0151 420 9595

www.betzdearborn.com/sentinel

FLUE TERMINAL GUARD:

PART No. 7 716 190 050

In the unlikely event the boiler does not give
complete satisfaction, before calling for a
service engineer, the installer should check
the following:-

General checks

1. Is the mode switch in boiler mode (indicator on)?

2. Is there 230V across the boiler live and neutral terminals?

3. Is the polarity correct? (230V across live and earth, 0V across neutral and earth)

4. Is the air bled from the primary system?

5. Is the air bled from the oil supply?

6. Is the flue sized and routed correctly?

Boiler runs straight to lockout

1. Has the oil line been purged of air?
2. Where an air eliminator is used in conjunction with a top feed oil tank

the non-return valve, (if fitted), should be removed from the oil dip pipe.

Boiler locks out at the start of a demand

(Heating off overnight for example)

1. If an air eliminator is being used, check that there are no leaks that allow

air to be pulled into the oil supply.

2. If a two pipe oil supply is a being used, has a non-return valve

been fitted to the inlet pipe? Refer to the instructions for guidelines.

No domestic hot water (external programmer)

1. Is the mains water in connected to the 15mm isolation valve?

2. Is there a domestic hot water demand from the programmer and has the

tank reached temperature?

3. Is there 230V on pin 2 of terminal block X4?

4. Remove the external wiring from terminal block X4 and fit a link across 1

and 2, if the domestic hot water now operates there is a problem with

the external programmer and/or its wiring.

No central heating (external programmer)

1. Are both programmer and room thermostat on demand for central heating?

2. Is the room thermostat wired correctly?

3. Refit the link across pins L

S

and L

R

on terminal X2, if the central heating

now operates correctly the room thermostat and/or its wiring are faulty.

4. Is there 230V on pin 1 of terminal block X4?

5. Remove the external wiring to terminal block X4 and fit a link across

pins 1 and 3 on terminal X4, if the central heating now operates correctly

the room programmer and/or its wiring are faulty.

EXCELLENCE COMES AS STANDARD

Worcester, Bosch Group

Cotswold Way, Warndon, Worcester WR4 9SW.

Tel. 01905 754624 Fax. 01905 754619

Worcester, Bosch Group is a trading name of BBT

Thermotechnology UK Ltd.

www.worcester-bosch.co.uk

8 716 113 389b (09/07)

UNDER NO CIRCUMSTANCES MUST AN APPLIANCE BE LEFT

TO OPERATE WITH ANY CONTROL LINKED OUT OR OVER RIDDEN.

Advertising
This manual is related to the following products: