Bryant GAMA 331JAV User Manual

Page 12

Advertising
background image

a. Inducer prepurge period—As inducer motor IDM comes

up to low speed or high speed, the low-heat pressure
switch contacts LPS (or LPS and HPS) close to begin a
15-sec prepurge period.

b. Ignitor warm-up—At the end of prepurge period, hot

surface ignitor HSI is energized for a 17-sec ignitor
warm-up period.

c. Trial-for-ignition sequence—When ignitor warm-up pe-

riod is completed, main gas valve relay contacts
MGVR-1 and -2 close to energize low-heat gas valve
solenoid GV, gas valve opens, and 24-v power is
supplied for a field-installed humidifier at terminals
HUM and C

OM

. Low-heat gas valve solenoid GV permits

gas flow to the burners where it is ignited. After 5 sec,
ignitor HSI is de-energized, and a 2-sec flame-proving
period begins.
If furnace control CPU selects high-gas-heat operation,
high-heat gas valve solenoid GV is also energized after
normally closed high-heat pressure switch relay HPSR
closes and after inducer motor IDM goes to high speed
and provides sufficient pressure to close high-heat pres-
sure switch HPS. HPSR is open while furnace is pow-
ered in standby mode. If high-heat pressure switch HPS
fails to close and low-heat pressure switch LPS closes,
furnace operates at low-heat gas flow rate until high-heat
pressure switch closes.

d. Flame-proving—When burner flame is proved at flame-

proving sensor electrode FSE, control CPU begins
blower on delay period and continues to hold gas valve
GV open. If burner flame is not proved within 2 sec,
control CPU closes gas valve GV, and control CPU
repeats ignition sequence for up to 3 more trials-for-
ignition before going to ignition lockout. LOCKOUT IS
RESET AUTOMATICALLY after 3 hr, or by momen-
tarily interrupting 115-v power to furnace, or by inter-
rupting 24-v power at SEC1 or SEC2 to control CPU
(not at W/W1, G, R, etc.). Opening thermostat R-W
circuit will not reset ignition lockout.
If flame is proved when flame should not be present,
control CPU locks out of gas heating mode and operates
inducer motor IDM on high speed until flame is no
longer proved.

e. Blower on delay—If burner flame is proven, 45 sec after

gas valve GV is opened blower motor BLWM is
energized on appropriate heating speed, low-gas-heat or
high-gas-heat speed. Simultaneously, EAC terminals
EAC-1 and EAC-2 are energized with 115v and remain
energized as long as blower motor BLWM is energized.

f. Switching from low- to high-gas heat—If furnace control

CPU switches from low-gas heat to high-gas heat,
control CPU switches inducer motor IDM speed from
low to high. The high-heat pressure switch relay HPSR
closes. When inducer motor IDM provides sufficient
pressure to close high-heat pressure switch HPS, high-
heat gas valve solenoid GV is energized. Blower motor
BLWM switches speed for high-gas heat 5 sec after
control CPU switches from low-gas heat to high-gas
heat.

g. Switching from high- to low-gas heat—Control CPU

will not switch from high-gas heat to low-gas heat while
thermostat R-W circuit is closed when a single-stage
thermostat is used.

h. Blower off delay—When thermostat is satisfied, R-W

circuit is opened, de-energizing gas valve GV, stopping
gas flow to burners, and de-energizing humidifier termi-
nals HUM and C

OM

. Inducer motor IDM remains ener-

gized for a 5-sec post-purge period. Blower motor
BLWM and EAC terminals EAC-1 and EAC-2 remain
energized for 90, 135, 180, or 225 sec (depending on
selection at blower off delay switches SW-3 and SW-4).
Furnace control CPU is factory set for a 135-sec blower
off delay.

2. Non-Adaptive Heating Mode—Two-Stage Thermostat and

2-Stage Heating
(See Fig. 12 for thermostat connections.)

NOTE: The low-heat-only switch SW-2 ON selects low-heat-

only operation mode in response to closing thermostat R-W/W1

circuit. When high-heat-only switch SW-1 is off, closing thermo-

stat R to W1-and-W2 circuits is required for high-gas-heat

operation. When high-heat-only switch SW-1 is on, it always

causes high-gas-heat operation when R-W/W1 circuit is closed,

regardless of setting of low-heat-only switch SW-2 and regardless

of whether R-W2 circuit is closed or open.

The start-up and shutdown functions and delays described

in item 1 above apply to 2-stage heating mode as well,

except for switching from low- to high-gas heat and vice

versa.
a. When wall thermostat "calls for heat," R-W/W1 circuit

closes for low-gas heat or R to W1-and-W2 circuits
close for high-gas heat. The furnace control performs a
self-check, verifies low-heat and high-heat pressure
switch contacts LPS and HPS are open, and starts
inducer motor IDM in low speed or high speed as
appropriate.

b. Switching from low- to high-gas heat—If thermostat

R-W/W1 circuit for low-gas heat is closed and R-W2
circuit for high-gas heat closes, control CPU switches
inducer motor IDM speed from low to high. The
high-heat pressure switch relay HPSR closes. When
inducer motor IDM provides sufficient pressure to close
high-heat pressure switch HPS, high-heat gas valve
solenoid GV is energized. Blower motor BLWM
switches speed for high-gas heat 5 sec after R-W2 circuit
closes.

c. Switching from high- to low-gas heat—If thermostat

R-W2 circuit for high-gas heat opens and R-W/W1
circuit for low-gas heat remains closed, control CPU
switches inducer motor IDM speed from high to low.
The high-heat pressure switch relay HPSR opens to
de-energize high-heat gas valve solenoid GV. When
inducer motor IDM reduces pressure sufficiently, high-
heat pressure switch HPS opens. The low-heat gas valve
solenoid GV remains energized as long as low-heat
pressure switch LPS remains closed. Blower motor
BLWM switches speed for low-gas heat 5 sec after
R-W2 circuit opens.

3. Cooling Mode

a. Single-Speed Cooling Outdoor Unit

(See Fig. 11 for thermostat connections.)
(1.) The thermostat closes R to G-and-Y circuits. The

R-Y circuit starts outdoor unit, and R to G-and-Y

circuits start furnace blower motor BLWM on

high-cool speed.

(2.) The EAC terminals EAC-1 and EAC-2 are ener-

gized with 115v when blower motor BLWM is

operating.

—12—

Advertising