CAUTION: Application of this furnace should be in-

doors with special attention given to vent sizing and

material, gas input rate, air temperature rise, and unit

sizing. Improper installation or misapplication of the

furnace can require excessive servicing or cause prema-

ture component failure.

Installation must conform to regulations of serving gas supplier
and local building, heating, and plumbing codes in effect in the
area in which installation is made, or in absence of local codes with
requirements of the NFGC.

This furnace is designed for a minimum continuous return-air
temperature of 60°F db or intermittent operation down to 55°F
such as when used with a night setback thermostat. Return-air
temperature must not exceed 85°F db.

To aid in installation, troubleshooting, and service, a status code
label is located on blower component door. This label explains
how to use the LED status indicated on furnace control which is
viewed through the sight glass on door.

WARNING: Improper installation, adjustment, alter-

ation, service, maintenance, or use can cause carbon

monoxide poisoning, explosion, fire, electrical shock, or

other conditions which may cause personal injury, loss of

life, or property damage. Consult a qualified installer,

service agency, local gas supplier, or your distributor or

branch for information or assistance. The qualified in-

staller or agency must use only factory-authorized and

listed kits or accessories when modifying this product. A

failure to follow this warning could result in electrical

shock, fire, personal injury, or death.

For high-altitude installation, the high-altitude conversion kit must
be installed at or above 5500 ft above sea level.

For accessory installation details, refer to applicable installation
literature.
NOTE: Remove all shipping brackets and materials before oper-
ating furnace.

Fig. 2—Clearances to Combustibles

A97620

32

2567

-101

REV

. E

(L

IT)

MINIMUM INCHES CLEARANCE TO COMBUSTIBLE CONSTRUCTION

INSTALLATION

This unit is certified for downflow installation only. See Installation Manual for

important installation instructions.

This forced air furnace is equipped for

use with natural gas at altitudes 0 -

10,000 ft

(0-3,050m).

An accessory kit, supplied by the

manufacturer, shall be used to convert to

propane gas use or may be required for

some natural gas applications.

This furnace is for indoor installation in

a building constructed on site.

This furnace may be installed on

combustible flooring in alcove or closet at

minimum clearance from combustible

material.

This furnace may be used with a Type

B-1 Vent and may be vented in common

with other gas-fired appliances.

Clearance in inches.

BO

TTO

M

##

1" #

0"

1"

1"

30"

MIN

S I

D E

F R

O N

T

B

C K

A

S E

R VI

E

C

F R

ON

T

S I

E

U

F

R N

A C

E

#

Ø

TO

P /

PL

EN

U

M

D

1"

Ø

For installation on non-combustible

floors only. For installation on

combustible flooring only when

installed on special base, Part No.

KGASB0201ALL, Coil Assembly,

Part No. CD5 or CK5, or Coil

Casing, Part No. KCAKC.

For furnaces wider than 14.25

inches (362mm) may be 0 inches.

18 inches front clearance required

for alcove.

For single wall vent type 6 inches.

#

##

Vent Clearance to combustibles:

For Single Wall vents 6 inches (6 po).

For Type B-1 vent type 1 inch (1 po).

This furnace is approved for DOWNFLOW installations only.