Bryant GAMA 331JAV User Manual

Page 4

Advertising
background image

I. LOCATION

A. General

CAUTION: DO NOT install furnace in a corrosive or

contaminated atmosphere. Make sure all combustion and

circulating air requirements are followed.

DO NOT use this furnace during construction when

adhesives, sealers, and/or new carpets are being installed

and curing. If the furnace is required during construction,

use clean outside air for combustion and ventilation.

Compounds of chlorine and fluorine when burned in

combustion air form acids which will cause corrosion of

the heat exchangers and metal vent systems. Some of

these compounds are released from paneling and dry wall

adhesives, paints, thinners, masonry cleaning materials,

and many other solvents commonly used in the construc-

tion process.

Excessive exposure to contaminated combustion air will

result in safety and performance related problems.

This furnace must be installed so electrical components are
protected from water.

Locate furnace as near to center of air distribution system and
chimney or vent as possible. The furnace should be installed as
level as possible.

When furnace is installed so that supply ducts carry air to areas
outside space containing furnace, the return air must also be
handled by a duct(s) sealed to furnace casing and terminating
outside space containing furnace.
Provide ample space for servicing and cleaning. Always comply

with minimum fire protection clearances shown on unit clearance

label. This furnace shall not be installed directly on carpeting, tile,

or any combustible material other than wood flooring. The furnace

may be installed on combustible flooring when installed with

accessory downflow subbase, which is available from your dis-

tributor or branch when required.

B. Location Relative to Cooling Equipment
The cooling coil must be installed parallel with or on downstream

side of furnace to avoid condensation in heat exchangers. When

installed parallel with furnace, dampers or other means used to

control the flow of air must prevent chilled air from entering

furnace. If dampers are manually operated, they must be equipped

with means to prevent operation of either unit unless damper is in

full-heat or full-cooling position.

C. Hazardous Locations
When furnace is installed in a residential garage, it must be

installed so that burners and ignition source are at least 18 in.

above floor. The furnace should be protected from physical

damage by vehicles.
When furnace is installed in public garages, airplane hangars, or

other buildings having hazardous atmospheres, unit must be

installed in accordance with recommended good practice require-

ments of the National Fire Protection Association, Inc.

II. AIR FOR COMBUSTION AND VENTILATION

Provisions for adequate combustion and ventilation air must be

provided in accordance with Section 5.3, Air for Combustion and

Ventilation, of the NFGC or applicable provisions of local building

codes.
Canadian installations must be in accordance with NSCNGPIC

and all authorities having jurisdiction.

CAUTION: Air for combustion must not be contami-

nated by halogen compounds which include fluoride,

chloride, bromide, and iodide. These elements are found

in aerosol sprays, detergents, bleaches, cleaning solvents,

salts, air fresheners, and other household products.

CAUTION: The operation of exhaust fans, kitchen ven-

tilation fans, clothes dryers, or fireplaces could create a

negative air pressure condition at the furnace. Make-up

air must be provided for these devices, in addition to that

required by the furnace.

All fuel-burning equipment must be supplied with air for combus-

tion of the fuel. Sufficient air MUST be provided to ensure there

will not be a negative pressure in equipment room or space. In

addition, a positive seal MUST be made between furnace cabinet

and return-air duct to avoid pulling air from the burner area and

draft safeguard opening into circulating air.
The requirements for combustion and ventilation air depend upon

whether furnace is located in a CONFINED or UNCONFINED

space.
A. Unconfined Space
An unconfined space must have at least 50 cu ft for each 1000

Btuh of input for all appliances (such as furnaces, clothes dryer,

water heaters, etc.) in the space.
For Example:

331JAV FURNACE

HIGH-FIRE INPUT

BTUH

MINIMUM SQ FT

WITH

7-1/2 FT CEILING

63,000

420

84,000

560

105,000

700

If the unconfined space is constructed unusually tight, air for

combustion and ventilation MUST come from either the outdoors

or spaces freely communicating with outdoors. Combustion and

ventilation openings must be sized the same as for a confined

space as defined below. Return air must not be taken from the

room unless equal or greater amount of air is supplied to the room.
B. Confined Space
A confined space is defined as a space whose volume is less than

50 cu ft per 1000 Btuh of total input ratings of all appliances

installed in that space. A confined space MUST have provisions

for supplying air for combustion, ventilation, and dilution of flue

gases using 1 of the following methods.
NOTE: In determining free area of an opening, the blocking

effect of louvers, grilles, and screens must be considered. If free

area of louver or grille design is unknown, assume that wood

louvers have a 20 percent free area and metal louvers or grilles

have a 60 percent free area. Screens, when used, must not be

smaller than 1/4-in. mesh. Louvers and grilles must be constructed

so they cannot be closed.
The size of the openings depends upon whether air comes from

outside of the structure or an unconfined space inside the structure.

1. All air from an unconfined space inside the structure

requires 2 openings (for structures not usually tight):

a. Each opening MUST have at least 1 sq in. of free area

per 1000 Btuh of total input for all equipment within the
confined space, but not less than 100 sq in. per opening.
(See Fig. 3 and Table 2.) The minimum dimension of air
openings shall not be less than 3 in.

b. If the building is constructed unusually tight, a perma-

nent opening directly communicating with the outdoors
shall be provided. (See item 2 below.)

—4—

Advertising