Bryant GAMA 331JAV User Manual

Page 16

Advertising
background image

TABLE 9—MODEL 331JAV ORIFICE SIZE AND MANIFOLD PRESSURE FOR CORRECT INPUT

(TABULATED DATA BASED ON 21,000 BTUH HIGH HEAT/13,500 BTUH LOW HEAT PER BURNER,

DERATED 4% FOR EACH 1000 FT ABOVE SEA LEVEL)

ALTITUDE

RANGE

(FT)

AVG GAS

HEAT VALUE

AT ALTITUDE

(BTU/CU FT)

SPECIFIC GRAVITY OF NATURAL GAS

0.58

0.60

0.62

0.64

0.66

Orifice

No.

Manifold

Pressure

High/Low

Orifice

No.

Manifold

Pressure

High/Low

Orifice

No.

Manifold

Pressure

High/Low

Orifice

No.

Manifold

Pressure

High/Low

Orifice

No.

Manifold

Pressure

High/Low

U.S.A.

and

Canada

850

42

3.3/1.4

42

3.4/1.4

42

3.5/1.5

42

3.7/1.5

42

3.8/1.6

875

43

3.8/1.6

42

3.2/1.3

42

3.3/1.4

42

3.5/1.4

42

3.6/1.5

900

43

3.6/1.5

43

3.7/1.5

42

3.2/1.3

42

3.3/1.3

42

3.4/1.4

0

925

43

3.4/1.4

43

3.5/1.5

43

3.6/1.5

43

3.8/1.6

42

3.2/1.3

950

44

3.7/1.5

44

3.8/1.6

43

3.5/1.4

43

3.6/1.5

43

3.7/1.5

to

975

44

3.5/1.5

44

3.6/1.5

44

3.8/1.6

43

3.4/1.4

43

3.5/1.4

1000

44

3.3/1.4

44

3.5/1.4

44

3.6/1.5

44

3.7/1.5

44

3.8/1.6

2000

1025

44

3.2/1.3

44

3.3/1.4

44

3.4/1.4

44

3.5/1.5

44

3.6/1.5

1050

45

3.7/1.5

45

3.8/1.6

44

3.2/1.3

44

3.4/1.4

44

3.5/1.4

1075

46

3.7/1.5

46

3.8/1.6

45

3.7/1.5

44

3.2/1.3

44

3.3/1.4

1100

46

3.5/1.5

46

3.6/1.5

46

3.8/1.6

45

3.7/1.5

45

3.8/1.6

ALTITUDE

RANGE

(FT)

AVG GAS

HEAT VALUE

AT ALTITUDE

(BTU/CU FT)

SPECIFIC GRAVITY OF NATURAL GAS

0.58

0.60

0.62

0.64

0.66

Orifice

No.

Manifold

Pressure

High/Low

Orifice

No.

Manifold

Pressure

High/Low

Orifice

No.

Manifold

Pressure

High/Low

Orifice

No.

Manifold

Pressure

High/Low

Orifice

No.

Manifold

Pressure

High/Low

U.S.A.

and

Canada

U.S.A.

775

43

3.7/1.5

42

3.2/1.3

42

3.3/1.4

42

3.4/1.4

42

3.5/1.4

Altitudes

800

43

3.5/1.4

43

3.6/1.5

43

3.7/1.5

42

3.2/1.3

42

3.3/1.3

2001

825

44

3.8/1.6

43

3.4/1.4

43

3.5/1.5

43

3.6/1.5

43

3.7/1.5

to

850

44

3.6/1.5

44

3.7/1.5

44

3.8/1.6

43

3.4/1.4

43

3.5/1.5

3000

875

44

3.4/1.4

44

3.5/1.4

44

3.6/1.5

44

3.7/1.5

44

3.8/1.6

or

900

44

3.2/1.3

44

3.3/1.4

44

3.4/1.4

44

3.5/1.4

44

3.6/1.5

Canada

925

46

3.8/1.6

45

3.8/1.6

44

3.2/1.3

44

3.3/1.4

44

3.4/1.4

Altitudes

950

46

3.6/1.5

46

3.7/1.5

45

3.7/1.5

45

3.8/1.6

44

3.2/1.3

2000

975

46

3.4/1.4

46

3.5/1.5

46

3.7/1.5

46

3.8/1.6

45

3.7/1.5

to

1000

47

3.7/1.5

47

3.8/1.6

46

3.5/1.4

46

3.6/1.5

46

3.7/1.5

4500

1025

47

3.5/1.5

47

3.6/1.5

47

3.8/1.6

46

3.4/1.4

46

3.5/1.5

ALTITUDE

RANGE

(FT)

AVG GAS

HEAT VALUE

AT ALTITUDE

(BTU/CU FT)

SPECIFIC GRAVITY OF NATURAL GAS

0.58

0.60

0.62

0.64

0.66

Orifice

No.

Manifold

Pressure

High/Low

Orifice

No.

Manifold

Pressure

High/Low

Orifice

No.

Manifold

Pressure

High/Low

Orifice

No.

Manifold

Pressure

High/Low

Orifice

No.

Manifold

Pressure

High/Low

U.S.A.

Only

750

43

3.5/1.4

43

3.6/1.5

43

3.7/1.5

42

3.2/1.3

42

3.3/1.4

775

44

3.8/1.6

43

3.4/1.4

43

3.5/1.4

43

3.6/1.5

43

3.7/1.5

800

44

3.5/1.5

44

3.7/1.5

44

3.8/1.6

43

3.4/1.4

43

3.5/1.4

3001

825

44

3.3/1.4

44

3.4/1.4

44

3.5/1.5

44

3.7/1.5

44

3.8/1.6

850

45

3.8/1.6

44

3.2/1.3

44

3.3/1.4

44

3.4/1.4

44

3.6/1.5

to

875

46

3.7/1.5

45

3.7/1.5

44

3.2/1.3

44

3.3/1.3

44

3.4/1.4

900

46

3.5/1.5

46

3.7/1.5

46

3.8/1.6

45

3.7/1.5

44

3.2/1.3

4000

925

47

3.8/1.6

46

3.5/1.4

46

3.6/1.5

46

3.7/1.5

46

3.8/1.6

950

47

3.6/1.5

47

3.7/1.5

46

3.4/1.4

46

3.5/1.5

46

3.6/1.5

975

47

3.4/1.4

47

3.5/1.5

47

3.7/1.5

47

3.8/1.6

46

3.4/1.4

1000

48

3.7/1.5

48

3.8/1.6

47

3.5/1.4

47

3.6/1.5

47

3.7/1.5

—16—

Advertising