g. Turn high-heat adjusting screw (5/64 hex Allen wrench)

counterclockwise (out) to decrease input rate or clock-
wise (in) to increase rate.

NOTE: DO NOT set high-heat manifold pressure less than 3.2-in.
wc or more than 3.8-in. wc for natural gas. If manifold pressure is
outside this range, change main burner orifices.

h. When correct input is obtained, replace caps that conceal

gas valve regulator adjustment screws. Main burner
flame should be clear blue, almost transparent. (See Fig.
16.)

i. Remove jumper R to W2.

4. Verify natural gas input rate by clocking gas meter.

a. Calculate high-altitude adjustment (if required).

UNITED STATES

At altitudes above 2000 ft, this furnace has been ap-
proved for a 4 percent derate for each 1000 ft above sea
level. See Table 8 for derate multiplier factor and
example.

EXAMPLE:
80,000 Btuh input furnace installed at 4300 ft.

Furnace Input

Rate at

Sea Level

X

Derate

Multiplier

Factor

=

Furnace Input Rate

at Installation

Altitude

80,000

X

0.82

=

65,600

CANADA

At installation altitudes from 2000 to 4500 ft, this
furnace must be derated 10 percent by an authorized Gas
Conversion Station or Dealer. To determine correct input
rate for altitude, see example above and use 0.82 as
derate multiplier factor.

b. Check that gas valve adjustment caps are in place for

proper input to be clocked.

c. Obtain yearly heat value average for local gas supply.

NOTE: Be sure heating value of gas used for calculations is

correct for your altitude. Consult local gas utility for altitude

adjustment of gas heating value.

d. Check and verify orifice size in furnace. NEVER AS-

SUME THE ORIFICE SIZE. ALWAYS CHECK AND
VERIFY.

e. Turn off all other gas appliances and pilots.
f. Move setup switch SW-2 to ON position. (See Fig. 13.)

This keeps furnace locked in low-heat operation.

g. Jumper R to W/W1.
h. Let furnace run for 3 minutes in low-heat operation.
i. Measure time (in sec) for gas meter to complete 1

revolution. Note reading.

j. Refer to Table 10 for cubic ft of gas per hr.
k. Multiply gas rate cu ft/hr by heating value (Btu/cu ft).
l. Move setup switch SW-2 to OFF position and jumper R

and W2 thermostat connections. (See Fig. 13.) This keeps
furnace locked in high-heat operation. Repeat items h
through k for high-heat operation.

EXAMPLE: (High-heat operation at 0—2000 ft altitude)

Furnace input from rating plate is 80,000 Btuh

Btu heating input = Btu/cu ft X cu ft/hr

Heating value of gas = 1050 Btu/cu ft

Time for 1 revolution of 2-cu ft dial = 92 sec

Gas rate = 80 cu ft/hr (from Table 10)

Btu heating input = 78 X 1050 = 81,900 Btuh

In this example, the orifice size and manifold pressure

adjustment is within

±2 percent of the furnace input rate.

NOTE: Measured gas inputs (high heat and low heat) must be

within

±2 percent of that stated on furnace rating plate when

installed at sea level or derated per that stated above when installed

at higher altitudes.

m. Remove jumper across R, W/W1, and W2 thermostat

connections to terminate call for heat.

5. Set temperature rise.

Place SW-2 in ON position. Jumper R to W/W1 and W2 to

check high-gas-heat temperature rise. To check low-gas-

heat temperature rise, remove jumper to W2. Determine air

temperature rise for both high and low heat using the

following steps. DO NOT exceed temperature rise ranges

specified on unit rating plate for high and low heat.

CAUTION: DO NOT redrill orifices. Improper drilling

(burrs, out-of-round holes, etc.) can cause excessive

burner noise and misdirection of burner flames. This can

result in flame impingement of burners and heat exchang-

ers, causing failures.

A93059

BURNER

ORIFICE

TABLE 8—ALTITUDE DERATE MULTIPLIER FOR U.S.A.

ALTITUDE

(FT)

% OF

DERATE

DERATE MULTIPLIER

FACTOR FOR U.S.A.*

0—2000

0

1.00

2001—3000

8—12

0.90

3001—4000

12—16

0.86

4001—5000

16—20

0.82

5001—6000

20—24

0.78

6001—7000

24—28

0.74

7001—8000

18—32

0.70

8001—9000

32—36

0.66

9001—10,000

36—40

0.62

* Derate multiplier factor is based on midpoint altitude for altitude range.