IV. FILTER ARRANGEMENT

WARNING: Never operate unit without a filter or with

filter access door removed. A failure to follow this

warning could result in fire, personal injury, or death.

The 2 factory-supplied filters are shipped in the blower compart-

ment. After return-air duct has been connected to furnace, install

filters in a V-formation inside return-air plenum. (See Fig. 8.)
V. GAS PIPING
Gas piping must be installed in accordance with national and local

codes. Refer to the NFGC NFPA 54-1996/ANSI Z223.1-1996.
Canadian installations must be installed in accordance with NSC-

NGPIC and all authorities having jurisdiction.

The gas supply line should be a separate line directly from the
meter to the furnace, if possible. Refer to Table 4 for recom-
mended gas pipe sizing. Risers should be used to connect to the
furnace and to the meter.

CAUTION: If flexible connector is required or allowed

by authority having jurisdiction, black iron pipe shall be

installed at gas valve and extend a minimum of 2 in.

outside furnace casing.

TABLE 2—FREE AREA OF COMBUSTION AIR OPENING

331JAV

FURNACE

HIGH-FIRE

INPUT

(BTUH)

AIR FROM

UNCONFINED

SPACE

OUTDOOR AIR THROUGH

VERTICAL DUCTS

OUTDOOR AIR THROUGH

HORIZONTAL DUCTS

OUTDOOR AIR THROUGH

SINGLE DUCT

Free Area

of Opening

(Sq In.)

Free Area of

Opening and Duct

(Sq In.)

Round

Pipe

(In. Dia)

Free Area of

Opening and Duct

(Sq In.)

Round

Pipe

(In. Dia)

Free Area of

Opening and Duct

(Sq In.)

Round

Pipe

(In. Dia)

63,000

100

15.8

5

31.5

7

21.0

6

84,000

100

21.0

6

42.0

8

28.0

6

105,000

105

26.3

6

52.5

9

35.0

7

TABLE 3—OPENING DIMENSIONS (IN.)

FURNACE

CASING

WIDTH

APPLICATION

PLENUM OPENING

FLOOR OPENING

A

B

C

D

14-3/16

Non-Combustible Flooring

12-11/16

19

13-3/8

19-5/8

Combustible Flooring Using KGASB Subbase

11-13/16

19

13-7/16

20-3/8

Combustible Flooring with CD5 or CK5 Coil Assembly or

KCAKC Coil Box

12-5/16

19

13-5/16

20

17-1/2

Non-Combustible Flooring

16

19

16-5/8

19-5/8

Combustible Flooring Using KGASB Subbase

15-1/8

19

16-3/4

20-3/8

Combustible Flooring with CD5 or CK5 Coil Assembly or

KCAKC Coil Box

15-1/2

19

16-1/2

20

21

Non-Combustible Flooring

19-1/2

19

20-1/8

19-5/8

Combustible Flooring Using KGASB Subbase

18-5/8

19

20-1/4

20-3/8

Combustible Flooring with CD5 or CK5 Coil Assembly or

KCAKC Coil Box

19

19

20

20

Fig. 5—Floor and Plenum Opening Dimensions

A96283

PLENUM

OPENING

C

A

B

D

FLOOR

OPENING

—6—