Bryant GAMA 331JAV User Manual

Page 19

Advertising
background image

a. Place duct thermometers in return and supply ducts as

near furnace as possible. Be sure thermometers do not
see heat exchangers so that radiant heat will not affect
thermometer readings. This is particularly important
with straight-run ducts.

b. When thermometer readings stabilize, subtract return-air

temperature from supply-air temperature to determine
temperature rise.

NOTE: If temperature rise is outside this range, first check:

(1.) Gas input for low- and high-heat operation.
(2.) Derate for altitude if applicable.
(3.) Return and supply ducts for excessive restrictions

causing static pressures greater than 0.50-in. wc.

c. Adjust air temperature rise by adjusting blower speed.

Increase blower speed to reduce temperature rise. De-
crease blower speed to increase temperature rise. For
high heat, speed selection can be med-high, med (5-
speed blowers only), or med-low (factory setting). For
low heat, speed tap selection can be low (factory setting),
med-low, or med (5-speed blowers only).

WARNING: Disconnect electrical power before chang-

ing speed tap (or removing cap on 5-speed motors). A

failure to follow this warning can cause personal injury or

death.

NOTE: For furnaces with 5-speed motors, ensure that unused

speed tap is either capped or placed on SPARE terminal on control

center before power is restored.

d. To change motor speed selection for high heat, remove

blower motor lead from control HIGH-GAS-HEAT
terminal. (See Fig. 10 and Fig. 14.) Select desired blower
motor speed lead from 1 of the other terminals and
relocate it to HIGH-GAS-HEAT terminal. See Table 11
for lead color identification. Reconnect original lead to
PARK terminal (or cover with insulating cap, if used in
furnaces using 5-speed blower motors). Follow this same
procedure for proper selection of cool and low-gas-heat
speed selection.

6. Set thermostat heat anticipator.

a. When using a nonelectronic thermostat, the thermostat

heat anticipation must be set to match amp draw of
electrical components in R-W/W1 circuit. Accurate amp
draw readings can be obtained at wires normally con-
nected to thermostat subbase terminals R and W/W1.
Fig. 17 illustrates an easy method of obtaining actual
amp draw. The amp reading should be taken after blower
motor has started and furnace is operating in low heat.
To operate furnace in low heat, first move SW-2 to ON
position, THEN connect ammeter wires as shown in Fig.

TABLE 10—GAS RATE (CU FT/HR)

SECONDS

FOR 1

REVOLUTION

SIZE OF TEST DIAL

SECONDS

FOR 1

REVOLUTION

SIZE OF TEST DIAL

1

cu ft

2

cu ft

5

cu ft

1

cu ft

2

cu ft

5

cu ft

10

11

12

13

14

360

327

300

277

257

720

655

600

555

514

1800

1636

1500

1385

1286

50

51

52

53

54

72

71

69

68

67

144

141

138

136

133

360

355

346

340

333

15

16

17

18

19

240

225

212

200

189

480

450

424

400

379

1200

1125

1059

1000

947

55

56

57

58

59

65

64

63

62

61

131

129

126

124

122

327

321

316

310

305

20

21

22

23

24

180

171

164

157

150

360

343

327

313

300

900

857

818

783

750

60

62

64

66

68

60

58

56

54

53

120

116

112

109

106

300

290

281

273

265

25

26

27

28

29

144

138

133

129

124

288

277

267

257

248

720

692

667

643

621

70

72

74

76

78

51

50

48

47

46

103

100

97

95

92

257

250

243

237

231

30

31

32

33

34

120

116

113

109

106

240

232

225

218

212

600

581

563

545

529

80

82

84

86

88

45

44

43

42

41

90

88

86

84

82

225

220

214

209

205

35

36

37

38

39

103

100

97

95

92

206

200

195

189

185

514

500

486

474

462

90

92

94

96

98

40

39

38

38

37

80

78

76

75

74

200

196

192

188

184

40

41

42

43

44

90

88

86

84

82

180

176

172

167

164

450

439

429

419

409

100

102

104

106

108

36

35

35

34

33

72

71

69

68

67

180

178

173

170

167

45

46

47

48

49

80

78

76

75

73

160

157

153

150

147

400

391

383

375

367

110

112

116

120

33

32

31

30

65

64

62

60

164

161

155

150

Fig. 15—Redundant Automatic Gas Control Valve

A97358

ON/OFF

SWITCH

INLET

PRESSURE

TAP

ON

O

F

F

MANIFOLD

PRESSURE

TAP

LOW-FIRE

ADJUSTMENT

ALLEN SCREW

(UNDER CAP)

HIGH-FIRE

ADJUSTMENT

ALLEN SCREW

(UNDER CAP)

Fig. 16—Burner Flame

A89020

;;

;;

BURNER FLAME

BURNER

MANIFOLD

—19—