background image

Brocade VDX 8770-4 Hardware Reference Manual

15

53-1002563-02

Preparing for the Brocade VDX 8770-4 installation

2

ensure that the bare copper wire has been cleaned and antioxidant is applied to the bare wire. In
addition, anti-rotation devices or lock washers must be used with all screw connections for the
grounding wire.

Environmental requirements

DANGER

Do not install the router in an environment where the operating ambient temperature might
exceed 40°C (104°F).

Table 5

lists the environmental operating ranges for the Brocade VDX 8770-4. The requirements for

non-operating conditions are also provided for acceptable storage and transportation
environments.

NOTE

The 0

°

to 40

°

C (32

°

to 104

°

F) range applies to the ambient air temperature at the air intake vents

on the left side (as you face the port side) and port side of the Brocade VDX 8770-4.

The temperature inside the Brocade VDX 8770-4 can be up to 90° C (194

°

F) for some modules

during operation. Brocade recommends that the internal temperature not exceed 75° C (167

°

F).

Cooling policy is based on a combination of ambient temperature and measured temperature on the
modules. Various combinations will result in an increase in fan speed to create more cooling in the
switch.
If a component approaches a critical temperature that will trigger a module shutdown, there will be
a WARNING message in the raslog, followed by a CRITICAL message saying that the module will shut
down in two minutes.
Use the show environment command to view temperature status.

TABLE 5

Environmental requirements

Condition

Acceptable range during operation

Acceptable range during non-operation

Ambient temperature

0

°

to 40

°

C (32

°

to 104

°

F) outside

switch

-25

°

to +70

°

C (-13

°

to 158

°

F) outside

switch

Humidity

5% to 90% RH noncondensing, at 40

° C

(104

°

F), with maximum gradient of 10%

per hour

10% to 90% RH noncondensing, at 70

°

C

(158

°

F)

Altitude

0 to 3 km (10,000 ft.) above sea level

0 to 12 km (40,000 ft.) above sea level

Shock

20G, 6 ms duration, half-sine wave

33G, 11 ms duration, half-sine wave

Vibration

0.5G p-p, 5-500 Hz at 1.0 octave/minute

2.0G p-p, 5-500 Hz at 1.0 octave/minute

Airflow

Maximum: 675 cu ft/min. (1147 cu
m/hr)
Nominal: 200 cu ft/min. (340 cu m/hr

None required

Maximum heat
dissipation

Up to 6000W or 20,500 BTU/hr

Not applicable

Advertising