2GIG CT100 User Manual

Page 15

Advertising
background image

14

PG

15

W

n

Y

n

R G

Multi-stage Heat and Multi-stage Cool

The CT100 can handle up to 2 stages of HEAT and 2 stages of COOL.

STEP 1 - Connect the W, W2 wires to the W terminals.

This connects the stages of HEAT.

STEP 2 - Connect the Y and Y2 wires to the Y terminals.

This connects the stages of COOL.

STEP 3 - Connect the RH or R wire to the RH terminal.

This connects the power.

STEP 4 - Connect the G wire to the G terminal.

This connects the fan.

STEP 5 - Optional - Connect the C wire to the C terminal.

Your HVAC system is now connected to the CT100.

Please Go To Page 6

Heat Pump (heat/cool) without Auxiliary Heat

STEP 1 - Connect O wire to the O terminal or B wire to the B terminal.

This connects the change-over valve.
IMPORTANT NOTE:

If you have both O and B - connect only the O wire to the O terminal and DO

NOT connect B to the B terminal (see wire reference under Trane for B wire terminal).

STEP 2 - Connect the Y wire to Y terminal. This connects the compressor.

STEP 3 - Connect the R wire to the RH terminal. This connects the power.

STEP 4 - Connect the G wire to the G terminal. This connects the fan.

STEP 5 - Optional - Connect the C wire to the C terminal.

Your HVAC system is now connected to the CT100.

Please Go To Page 6