Electrical hazard – Snorkel TB120 2001 User Manual

Page 2

Advertising
background image

P/N 0191914

D A N G E R

ELECTRICAL HAZARD

The TB120 is an all metal boom, NOT ELECTRICALLY INSULATED, aerial work platform. Do
not operate it near ELECTRICAL conductors. Regard all conductors as being energized. Use
the table and figure below to determine safe clearance from electrical conductors. Table 1 and
Figure 3 are reprinted courtesy of Scaffold Industry Association, ANSI/SIA A95, page 23.

Figure 3 - Minimum Safe Approach Distance (M.S.A.D.)

Table 1 - Minimum safe approach distance (M.S.A.D.)

to energized (exposed or insulated) power lines

Voltage range

(phase to phase)

Minimum safe approach distance

(Feet) (Meters)

0 to 300V

Avoid contact

Over 300V to 50KV

10

3.05

Over 50KV to 200KV

15

4.60

Over 200KV to 350KV

20

6.10

Over 350KV to 500KV

25

7.62

Over 500KV to 750KV

35

10.67

Over 750KV to 1000KV

45

13.72

Danger: - Do not allow machine personnel or conductive
materials inside prohibited zone.

- Maintain M.S.A.D. from all energized lines and parts
as well as those shown.

- Assume all electrical parts and wires are energized
unless known otherwise.

Caution: - Diagrams shown are only for purposes of illustrating
M.S.A.D. work positions, not all work positions.

Advertising