SECTION 6 - JLG CONTROL SYSTEM

3120772

– JLG Lift –

6-15

2/5

Flash code 2/5 indicates that a function is prevented due to a cutout.

BOOM PREVENTED - DRIVE SELECTED
A boom function is selected while a drive function is selected and drive cutout is configured to prevent
simultaneous drive & boom operation.

BOOM PREVENTED - FUNCTION CUTOUT ACTIVE
A boom function is selected while function cutout is active and configured to cutout boom functions.

DRIVE & BOOM PREVENTED - FUNCTION CUTOUT ACTIVE
Drive or a boom function is selected while function cutout is active and configured to cutout all functions.

DRIVE PREVENTED - ABOVE ELEVATION
Drive is selected while above elevation and drive cutout is configured to prevent drive.

DRIVE PREVENTED - BOOM MOVEMENT SELECTED
Drive is selected while a boom function is selected and drive cutout is configured to prevent simultaneous
drive & boom operation.

DRIVE PREVENTED - CHARGER CONNECTED
Drive is selected while the charger is on (indicated by drive cutout being active) and drive cutout is config-
ured to prevent drive.

DRIVE PREVENTED - TILTED ABOVE ELEVATION
Drive is selected while drive cutout is active and drive cutout is configured to prevent drive.

3/1

Flash code 3/1 indicates that a contactor did not close when energized.

LINE & DIRECTION CONTACTORS MISWIRED
When the line contactor was closed traction point A went high (and the capacitor bank charge did not
increase to battery supply) - this occurs if the line contactor coil wiring is swapped with that for a direction
contactor coil.

OPEN-CIRCUIT FORWARD DIRECTION CONTACTOR OR TRACTION MOTOR
Traction point A did not go high when forward contactor was energized (this could be due to traction motor
open-circuit or a power wiring error).

OPEN-CIRCUIT LINE CONTACTOR
The capacitor bank charge did not increase to battery supply when line contactor was energized (this could
be due to a power wiring error).

OPEN-CIRCUIT REVERSE DIRECTION CONTACTOR OR TRACTION MOTOR
Traction point A did not go high when reverse contactor was energized (this could be due to traction motor
open-circuit or a power wiring error).

3/2

Flash code 3/2 indicates that a contactor did not open when energized.

WELDED LINE CONTACTOR
The capacitor bank charge did not decrease from battery supply when line contactor was deenergized (this
could be due to a power wiring error).
WARNING: If the line contactor is welded, the controller will not switch off when EMS or key switch is turned
off.

3/3

Flash code 3/3 indicates that a contactor coil is short-circuited.

OVERLOADED VALVE SUPPLY-CHECK WIRING.
There is a high current draw from the valve supply when no valve is energized; this is probably due to a wir-
ing error at the ground module.

SHORT-CIRCUIT FORWARD CONTACTOR COIL
The forward contactor was not energized when required, due to coil over current protection.

SHORT-CIRCUIT LINE CONTACTOR COIL
The line contactor was not energized when required, due to coil over current protection.

SHORT-CIRCUIT REVERSE CONTACTOR COIL
The reverse contactor was not energized when required, due to coil over current protection.

Table 6-5. Help Descriptions and Fault Flash Codes